Permit NumberGCB13-00112
StatusFinaled
Name Lance Hale
Site Address 6708 N GLENWOOD BLVD
Project NameBLD2013-00110
Customer Number 
ePlanReviewNo
Description
DICKEY'S BARBECUE PIT - To remodel an existing 2,263 square foot tenant space in an existing 28,438 square foot shopping center building for use as a Restaurant Assembly occupancy per plans. Work to include: construction of interior non-bearing walls to create separation from the customer dining area and the commercial kitchen areas, and exit corridor; installation of new HVAC unit on the roof per engineering; install new Type-1 kitchen hoods; installation of suspended acoustical ceilings; related interior finishes in compliance with chapter 8 of the 2009 IBC; plumbing, electrical and mechanical work. All work per the approved plans, attached plan review report, and all other reviewing agencies approvals. The maximum occupant load of the Restaurant Dining room shall be 72 persons and shall be posted in a conspicuous place near the main exit. A new Certificate of Occupancy with the new occupant load total is required to be obtained after all work has been inspected and approved and prior to tenant occupying this space. "This building is fully Fire Sprinklered for area increase. Any alterations or modifications to the buildings Fire Sprinkler WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 as regulated by the Boise Fire Department." **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCB-Final12/11/201312/11/201312/11/2013PPASS
DetailsMike Jordan
All issues have been resolved. Structural final only ok.
GCB-Final12/10/201312/11/201312/11/2013ANR
DetailsMike Jordan
Vaughn ###-#### call for access. contractor noted that this inspection was supposed to be a pm inspection?
GCB-Ceiling Grid12/9/201312/10/201312/10/2013APASS
DetailsMike Jordan
Ron ###-#### Please make sure framing inspection results are entered as well. Ron said framing inspect was already done.
GCB-Framing12/10/201312/10/201312/10/2013APASS
DetailsMike Jordan
Ron ###-#### Please make sure framing inspection results are entered as well. Ron said framing inspect was already done. A framing inspection has been completed. They are listed under the footing inspections. (wrong inspection detail). Notes under these inspections do indicate framing was inspected.
GCB-Final12/9/201312/10/201312/10/2013AFAIL
DetailsMike Jordan
Ron ###-#### Make sure framing/and ceiling inspects are done and in system please. Provide panic hardware at rear exit, install exterior emergerncy lighting at front enterance, provide lock indicator at main enterance/exit. Also install the vertical grabbars in restrooms.
GCB-Footing11/5/201311/6/201311/6/2013APASS
DetailsMike Jordan
Vaughn ###-####. soffitt is now ok to cover.
GCB-Footing10/30/201310/30/201310/30/2013PFAIL
DetailsMike Jordan
Vaughn ###-####. Provide RFI from architect for in place soffit framing, not per detail 6 on sheet A3.1. Correction notice posted.