Permit Information
Permit NumberGCE09-00044
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 5555 N Glenwood Blvd
Project NameELE2009-00044
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final1/14/20101/15/20101/15/2010APASS
DetailsDoug A Poedy
Contact Zen @ ###-####. Ok final.
GCE-Final1/13/20101/14/20101/14/2010ANR
DetailsDoug A Poedy
Contact Zen @ ###-####. No access to one of the large rooms. It was sealed off and being painted.
GCE-Rough-In1/4/20101/5/20101/5/2010APASS
DetailsJack Frank
Contact Zen @###-#### ceilings ok
GCE-Rough-In12/30/200912/31/200912/31/2009AFAIL
DetailsBob Reichert
Contact Zen @###-####Please contact Zen prior to come in for inspection.The applicant wants the inspector to look at electrical Ceiling. called, left correction notice, NEC 362.30(A) ent shall be securely fastened within 3' of box and every 3', 330.30(B) mc cable shall be secured within 12" of boxes, 110.12(A) shall close boxes- install cover,725.25 accessible portions of abandoned cl 2,3, pltc cables shall be removed, 300.11(A) cables and raceways shall not be supported by ceiling grids, no esc this project
GCE-Rough-In12/21/200912/22/200912/22/2009APASS
DetailsDoug A Poedy
Contact Zen @###-####. Ok to cover all walls.
GCE-Rough-In12/18/200912/21/200912/21/2009APART
DetailsDoug A Poedy
For any questions, contact Zen @###-####. Ok to cover worship room ceiling.
GCE-Rough-In12/18/200912/18/200912/18/2009PNR
DetailsJack Frank
zen Phone #: ###-#### see am request
GCE-Rough-In12/17/200912/18/200912/18/2009ANR
DetailsJack Frank
Contact Zen @###-#### still needs fire alarm system dropped to new hard ceiling, too many 4 sq extensions on exit light boxes also free length of conductor met contr on job
GCE-Rough-In12/15/200912/17/200912/17/2009AFAIL
DetailsDoug A Poedy
Contact Zen@###-####. Inspection was for left hand side of building. Ceiling is going to be hard lid and there are many j-boxes that will no longer be accessible. NEC 314.29