Permit NumberGCE15-00171
StatusFinaled
Name Amp Electric
Site Address 430 E 51ST
Project NameELE2015-00170
Customer Number 
ePlanReviewNo
Description
GCB15-00092
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
GCE-Final1/28/20161/29/20161/29/2016APASS
DetailsRex Boyles
Greg ###-#### corrections made final ok
GCE-Final1/27/20161/28/20161/28/2016AFAIL
DetailsRex Boyles
Greg ###-#### corrections not made
GCE-Final1/26/20161/27/20161/27/2016AFAIL
DetailsRex Boyles
Greg ###-#### - garage code: 3255 Reverse polarity to dining rm receptacle, no cover 2gang box kitchen counter, identify o/s receptacle circuit
GCE-Rough-In Permanent Service12/13/201512/10/201512/14/2015ADONE
DetailsRex Boyles
Greg ###-#### already inspected ??
GCE-Rough-In Permanent Service12/9/201512/10/201512/10/2015APASS
DetailsRock A. Hudson
Greg ###-#### Rough in ok cover
p/s u/g n ok
GCE-Rough-In12/9/201512/9/201512/9/2015PFAIL
DetailsRex Boyles
Greg ###-#### 210.52(G)(1)- the branch circuit supplying garage receptacles shall not supply outlets outside of the garage. metal boxes shall be grounded at rough in stage 320.23(A)- cables run within 6 foot of attic crawl shall be protected with gaurd strips. remove all drywall covering full length of nm cable not yet inspected