Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberMEC03-01360
StatusFinaled
Name INTERMOUNTAIN PIPE
Site Address 1673 W SHORELINE DR Unit: 100
Project NameRIVERWALK CENTER
Customer Number 
ePlanReview 
Description
GAS PIPING FROM METER TO HVAC UNITS ON THE ROOF PER INITIAL CERT OF VALUE $2,200.00///Final cert of value $2,200///5/7/04 BAM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/22/20037/23/20037/23/2003APASS
DetailsAlan Hauser
Scheduled by a contractor via Hello! on 7/22/2003 at 10:07:44 PM. Contact: ###-####.
Final7/21/20037/22/20037/22/2003ANR
DetailsAlan Hauser
code requires full size flex, same as opening into appliance, and hvac hasn't finished vent to water heater 7/22/2003 8:02:58 PM
Pressure Test7/3/20037/3/20037/3/2003PPASS
DetailsAlan Hauser
kirk; Phone #: ###-#### Internet Inspection Request from: Darla Downs
Pressure Test7/2/20037/2/20037/2/2003PFAIL
DetailsAlan Hauser
pressure has dropped on test 7/3/2003 1:04:18 AM
Pressure Test5/30/20035/30/20035/30/2003PFAIL
DetailsAlan Hauser
RTU'S are larger in btu size than shown on plan, need to recheck pipe sizing to see if will work 5/30/2003 11:33:51 PM