Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberMEC04-03306
StatusFinaled
Name BS & R EQUIPMENT CO INC
Site Address 7709 W OVERLAND RD
Project NameTHE BOISE SPECTRUM
Customer Number 
ePlanReview 
Description
Installing class 1 cooking hood and duct work per initial cert of value $7,400///11/22/04 BAS/// Final cert of value $7,925///3/11/05 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/14/20051/18/20051/18/2005APASS
DetailsTroy James
rich or jr ###-####; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Conference1/12/20051/13/20051/13/2005ADONE
DetailsTroy James
9:00 am 9:00 am discussed grease duct installation requirements at roof 1/13/2005 9:16:49 AM
Final1/7/20051/7/20051/7/2005PFAIL
DetailsTroy James
jr Note: exhaust hood; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
grease exhaust to close to parapet wall, need fire wrap where penetrate roof, grease duct at exhaust fan has no slope to duct, air balance does not meet required design per code. 1/7/2005 4:00:10 PM
Rough-in11/30/200411/30/200411/30/2004PPART
DetailsDixie Fellows