Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberMEC13-00287
StatusFinaled
Name BUSS MECHANICAL SERVICES INC
Site Address 800 W MAIN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - New: HYDRONIC PIPING, GAS PIPING, AND EQUIPMENT
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/4/201311/5/201311/5/2013APASS
DetailsTroy James
JOB CONTACT IS COLI Phone #: ###-#### >> Inspection requested via web by ADAM WARR
Final10/31/201311/1/201311/1/2013PPART
DetailsTroy James
contact is Colin ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
need to check to see if over protection device required downstream of gas regulator
Pressure Test10/15/201310/16/201310/16/2013PPASS
DetailsTroy James
JOB CONTACT IS COLIN Phone #: ###-#### >> Inspection requested via web by ADAM WARR
final connection to meter
Pressure Test10/3/201310/4/201310/4/2013APASS
DetailsTroy James
CONTACT IS COLIN ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
ok pressure test to heating pipes
Pressure Test9/20/20139/20/20139/20/2013PPASS
DetailsTroy James
JOB CONTACT - COLIN ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER
ok 60# test to gas line, ok test to fluid cooler condenser
Pressure Test5/23/20135/24/20135/28/2013PPART
DetailsBill VanDegrift
JOB CONTACT - KEITH ###-####
17TH FLOOR Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER 17th floor loop test ok
Rough-in5/6/20135/7/20135/9/2013APART
DetailsBill VanDegrift
contact is Keith ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS 16th floor hydronic loop test ok
Rough-in4/22/20134/22/20134/22/2013PPASS
DetailsTroy James
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR
ok hydronics in shaft a 16 to penthouse
Rough-in4/17/20134/18/20134/18/2013PPASS
DetailsTroy James
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR
ok 15th floor hydronics
Pressure Test4/10/20134/10/20134/11/2013PPASS
DetailsTroy James
CONTACT IS KEITH ###-####. INSPECTION IS FOR HYDRONIC PIPING. Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
ok test and piping at 14th floor
Rough-in4/2/20134/3/20134/3/2013APASS
DetailsTroy James
JOB CONTACT - KEITH
16TH FLOOR Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER
ok hydronic 13th floor
Pressure Test3/25/20133/26/20133/26/2013APASS
DetailsTroy James
Inspection is for 14th-16th floor. contact is Keith ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
ok hydronics in shaft for floors 14-16
Pressure Test3/15/20133/18/20133/18/2013APASS
DetailsTroy James
JOB CONTACT - KEITH ###-####
PARTIAL PRESSURE TEST ON 11TH AND 12TH FLOOR Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER
hydronics floors 11 and 12, shaft up to 16th floor and gas piping up to 16th floor
Pressure Test3/8/20133/11/20133/11/2013APASS
DetailsTroy James
keith ###-####
ok test to hydronic on the 10th and 11th floor.
Pressure Test3/8/20133/8/20133/8/2013PCANC
DetailsBill VanDegrift
keith ###-#### oops wrong day
Pressure Test3/7/20133/8/20133/8/2013ACANC
DetailsBill VanDegrift
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR sent to Troy for manday
Pressure Test2/26/20132/26/20132/26/2013PPASS
DetailsTroy James
contact is colin ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
ok hydronic 8th floor and shaft to 14th floor and ok 80# test to gas line in shaft to 14th floor.
Rough-in2/12/20132/13/20132/13/2013PPASS
DetailsTroy James
JOB CONTACT - KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER
ok hydronics to 2, 6, and 7 floor and pipe in shaft to 9th floor
Pressure Test2/4/20132/4/20132/4/2013APASS
DetailsTroy James
gas and condensation line test in shaft
60 # test to natural gas line from meter base to 9th floor, 150# test to condenser lines to 9th floor in shaft.
Pressure Test1/23/20131/24/20131/25/2013PPASS
DetailsTroy James
CONTACT IS COLIN ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS
ok risers to the 9th floor and the branches at the 3rd, 4th, and 5th floor