Information based on query as of Saturday, July 6, 2024.
Permit Information
Permit NumberMEC13-01311
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 200 W BROAD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - New: new hvac system and infloor readiant
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/26/20137/26/20137/26/2013PPASS
DetailsTroy James
Will resubmit plan mod for smoke detectors at each return inlet. Fire inspector will look at smoke detectors.
Final7/26/20137/26/20137/26/2013PFAIL
DetailsTroy James
please call john with any questions
Phone #: ###-#### >> Inspection requested via web by Nicholas Paige
Plan mod approved by fire plan reviewer has been approved without given full information. Plan mod is now not approved. Cannot approve final until the smoke detector to heat pumps design has been approved. We have open return serving three separate areas.
Final7/17/20137/19/20137/22/2013AFAIL
DetailsTroy James
please call John with any questions Phone #: ###-#### >> Inspection requested via web by Nicholas Paige
Need smoke detectors to 3 mechanical units north east side of building.
Pressure Test6/24/20136/24/20136/24/2013PPART
DetailsAlan Hauser
Hydronic Pressure Test ok on all above ground hydronics
Conference6/21/20136/21/20136/21/2013APART
DetailsBill VanDegrift
will need RTU's for ventilation
Rough-in6/18/20136/18/20136/18/2013PPART
DetailsDixie Fellows
please call Doran with any questions Phone #: ###-#### >> Inspection requested via web by Nicholas Paige...OK TO COVER HYDRONICS IN ALL WALLS
Rough-in6/7/20136/11/20136/11/2013APART
DetailsTroy James
please call john with any questions, this is a cover inspection Phone #: ###-#### >> Inspection requested via web by Nicholas Paige
ok to cover hard lid and walls only
Rough-in5/29/20135/29/20135/29/2013PPASS
DetailsDixie Fellows
Partial cover inspection Phone #: ###-#### >> Inspection requested via web by Nicholas Paige..ok to wrap
Rough-in4/16/20134/17/20134/18/2013PPASS
DetailsDixie Fellows
please call doran with any questions. this is a rough in for underground radiant tubing Phone #: ###-#### >> Inspection requested via web by Nicholas Paige...100lb test on remaining u/g tubing ok
Rough-in4/4/20134/4/20134/4/2013PPART
DetailsBill VanDegrift
This is for the in floor radiant tubing rough in please call doran with any questions! Phone #: ###-#### >> Inspection requested via web by Nicholas Paige 4 - radiant test ok