Final | 10/6/2014 | 10/7/2014 | 10/7/2014 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey
|
Conference | 8/15/2014 | 8/15/2014 | 8/15/2014 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey Inspection cancelled from web by: Aaron Toomey
|
Pressure Test | 8/14/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey - 20LB GAS PRESSURE PASS, 5LB FLUE PRESSURE PASS
|
Rough-in | 8/14/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey
|