Permit Information
Permit NumberMEC15-03751
StatusFinaled
Name COX MECHANICAL INC
Site Address 1612 S BROADWAY AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: furnish and install 3each rtus
furnish and install 1 each RR exhaust fan
air distribution
install owner furnished hood and exhaust fans
furnish and install 16ga welded duct with fire wrap for grease ducts
tstats and sensors
air balance
control pane
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/25/20159/25/20159/25/2015PPASS
DetailsChad Schwendiman
just in case Phone #: ###-#### Inspection requested via web by Robin Cox
Final9/24/20159/25/20159/25/2015APEND
DetailsChad Schwendiman
a final for Friday 9-25-15 in the am. Phone #: ###-#### Inspection requested via web by Robin Cox - Pending air balance report
Rough-in9/16/20159/17/20159/17/2015APASS
DetailsChad Schwendiman
duct detectors are in. no power. will be able to test at final. need to put ceiling tiles in. thanks Phone #: ###-#### Inspection requested via web by Robin Cox - Okay to cover ceiling. The kitchen equipment isn't all set into place yet, but I called and told Robin that I am concerned about the hood being big enough to over hang the equipment by 6" on all open sides.
Final9/15/20159/15/20159/15/2015PFAIL
DetailsChad Schwendiman
final for Tuesday 9-15-15 for the afternoon Phone #: ###-#### Inspection requested via web by Robin Cox -
1) supply grills not installed yet.
2) need cooking equipment installed under hood.
3) need a copy of the air balance report.
4) duct smoke detectors not installed
5) flue exhaust hoods not installed on RTU's
Rough-in9/2/20159/3/20159/3/2015APASS
DetailsChad Schwendiman
inspect first layer of fire wrap on grease duct Phone #: ###-#### Inspection requested via web by Robin Cox
Rough-in8/29/20158/31/20158/31/2015APASS
DetailsChad Schwendiman
light test for grease duct. please call Robin to let him know what time. ###-#### Phone #: ###-#### Inspection requested via web by Robin Cox
Rough-in8/18/20158/19/20158/19/2015APART
DetailsChad Schwendiman
Duct sealer for 8-19-15 morning Phone #: ###-#### Inspection requested via web by Robin Cox - duct seal pass
Conference8/12/20158/13/20158/13/2015ADONE
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Robin Cox - Discussion in regards to clearance from back of hood to wall. with the way the hood was made it will require a 2" stand off in order to have the required clearance to the grease duct
Rough-in8/12/20158/12/20158/12/2015PPASS
DetailsChad Schwendiman
rough in for the bathrooms Phone #: ###-#### Inspection requested via web by Robin Cox - okay to cover bathroom ceilings