Final | 5/29/2018 | 5/30/2018 | 5/30/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Final | 5/24/2018 | 5/29/2018 | 5/29/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - return transfer in front office is undersized, still need p-trap on RTU condensate
|
Final | 5/22/2018 | 5/23/2018 | 5/23/2018 | A | PART |
Chad Schwendiman
|
|
|
Whole Bldg please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Temporary occupancy okay. Missing return/transfer ducts and grills in office area, missing condensate p-trap on rtu
|
Final | 5/21/2018 | 5/22/2018 | 5/22/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Whole building Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Missing fire damper in trash room, missing duct access doors for fire/smoke dampers in 4th floor mech room, need screws every 6" on retaining angles on dampers in 4th floor mechanical room, missing return and return transfers in office area, need to secure fans and hoods to curbs on roof, need completed generator commisioning report.
|
Conference | 5/10/2018 | 5/10/2018 | 5/10/2018 | A | DONE |
Chad Schwendiman
|
|
|
Phone ###-#### - Discussed relocating an exhauast penetration
|
Final | 4/27/2018 | 4/27/2018 | 4/27/2018 | P | FAIL |
Ben Livingston
|
|
|
Rooftop final please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN condensates on 1st 2nd 3rd floor okay, all line sets need to be supported and connected to support
|
Final | 4/17/2018 | 4/18/2018 | 4/18/2018 | A | PART |
Chad Schwendiman
|
|
|
Final inspection for 1st 2nd and 3rd floors please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - final okay on units 300, 302, 303, 304, 305, 306, 202, 203, 204, 205, 206, 103, 104, 105, 106, 126.
Condensates not complete in units 301, 200, 201, 100, 101, 102
|
Conference | 4/13/2018 | 4/13/2018 | 4/13/2018 | P | PASS |
Chad Schwendiman
|
|
|
Cover inspection for garage please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover garage ceiling
|
Final | 4/3/2018 | 4/3/2018 | 4/3/2018 | P | PART |
Chad Schwendiman
|
|
|
3rd ; 4th floors 2nd phase please Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - finals okay on units 112, 124, 320, 322, 323, 324, 325, 326, 328, 330, 332, 401, 402, 403, 405, 406, 420, 423, 425, 432
|
Final | 4/2/2018 | 4/2/2018 | 4/2/2018 | P | PART |
Chad Schwendiman
|
|
|
partial final for phase two, floors 1,2,3 & 4 // Justin Phone #: ###-#### - final okay on units 120, 122, 123, 125, 128, 130, 132, 220, 222 223, 224, 225, 226, 228, 230, 232
|
Final | 3/28/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in lobby area
|
Final | 3/23/2018 | 3/26/2018 | 3/26/2018 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover ceilings in fitness room and club house. Final okay on units 107, 108, 109, 110, 111, 114, 116, 118
|
Final | 3/21/2018 | 3/21/2018 | 3/21/2018 | P | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN units 408, 308, 207, 208, 209, 210, 211, 212, 214, 216, 218
|
Rough-in | 3/17/2018 | 3/19/2018 | 3/19/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Fire/smoke damper instalation and clearances okay on fourth floor south shaft.
|
Final | 3/12/2018 | 3/12/2018 | 3/12/2018 | A | PART |
Chad Schwendiman
|
|
|
3rd and 4th floor Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - apt's 307, 310, 309, 312, 314, 311, 316, 318, 407, 409, 410, 411, 412, 414, 416, 418
|
Rough-in | 3/6/2018 | 3/6/2018 | 3/6/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to sheetrock the face of the north shaft on all floors, Okay to sheetrock the face of the south east shaft on 1st-3rd floors
|
Rough-in | 3/1/2018 | 3/1/2018 | 3/1/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover south east shaft on 1st, 2nd, and 3rd floors
|
Rough-in | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 2/28/2018 | 2/28/2018 | 2/28/2018 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in unit 300. Need framing around fire/smoke dampers on south east shaft
|
Rough-in | 2/23/2018 | 2/26/2018 | 2/26/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in units 100, 101, 102, 103, 104, 105, 106
|
Rough-in | 2/22/2018 | 2/22/2018 | 2/22/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - duct seal okay on exhaust shaft in north corridoor
|
Rough-in | 2/21/2018 | 2/21/2018 | 2/21/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in units 200, 201, 202, 203, 204, 205, 206
|
Rough-in | 2/14/2018 | 2/15/2018 | 2/15/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - unit 301 okay to cover hard lids
|
Rough-in | 2/14/2018 | 2/14/2018 | 2/14/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 302, 303, 304, 305, 306 okay to cover hard lids.
|
Rough-in | 2/13/2018 | 2/13/2018 | 2/13/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in units 401, 402, 403, 404, 405, 406
|
Rough-in | 2/7/2018 | 2/7/2018 | 2/7/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lids in units 425, 432, and 2nd floor janitors room
|
Rough-in | 2/6/2018 | 2/6/2018 | 2/6/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in units 420, 423, and the 4th floor janitors room
|
Rough-in | 2/5/2018 | 2/5/2018 | 2/5/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover walls and TGI's in unit 300
|
Rough-in | 2/1/2018 | 2/1/2018 | 2/1/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN okay to cover hard lids in units 320, 325, 330, 332
|
Rough-in | 1/30/2018 | 1/31/2018 | 1/31/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover hard lids in units 132, 232, 322, 323, 324, 326, 328
|
Rough-in | 1/26/2018 | 1/26/2018 | 1/26/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lids in units 216, 218, 220, 222, 223, 224, 226, 228, 225, 230
|
Rough-in | 1/24/2018 | 1/24/2018 | 1/24/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lid in unit 125
|
Rough-in | 1/23/2018 | 1/23/2018 | 1/23/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - hard lids okay to cover in 122, 123, 124, 126, 128
|
Rough-in | 1/18/2018 | 1/18/2018 | 1/18/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lids in units 116, 118, 120
|
Rough-in | 1/16/2018 | 1/16/2018 | 1/16/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover walls and TGI's in units 402, 403, 404, 405, 406
|
Rough-in | 1/11/2018 | 1/11/2018 | 1/11/2018 | P | PASS |
Chad Schwendiman
|
|
|
3rd floor ; 401 Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover walls and TGI's in units 302, 303, 304, 305, 306, 401
|
Rough-in | 1/9/2018 | 1/9/2018 | 1/9/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lids in units 407, 408, 409, 410, 411, 412, 414, 416, 418
|
Rough-in | 1/5/2018 | 1/5/2018 | 1/5/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover walls and tgi's in units 200-206m and 301
|
Rough-in | 1/3/2018 | 1/3/2018 | 1/3/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN 0kay to cover walls and bottom of TGI's in units 100, 101, 102, 103, 104, 105, 106
|
Rough-in | 12/27/2017 | 12/27/2017 | 12/27/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover hard lids 307,308,309, 310, 311, 312, 314, 316, 318
|
Rough-in | 12/11/2017 | 12/12/2017 | 12/12/2017 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN prerock 325,330,332,420,423,425
|
Rough-in | 12/8/2017 | 12/8/2017 | 12/8/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover walls and TGI's in units 322, 326, 328
|
Rough-in | 12/7/2017 | 12/7/2017 | 12/7/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN okay to cover walls and TGI's in units 320, 323, 324
|
Rough-in | 12/4/2017 | 12/5/2017 | 12/5/2017 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 12/4/2017 | 12/5/2017 | 12/5/2017 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN okay to cover walls and tgi's in units 123, 124, 125, 126, 128, 130, 132, 223, 224, 225, 226, 228, 230, 232
|
Rough-in | 12/1/2017 | 12/1/2017 | 12/1/2017 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN 207-214 okay
|
Pressure Test | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 60lb gas
|
Rough-in | 11/27/2017 | 11/27/2017 | 11/27/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover bottomg of TGI's and walls in units 120, 122, 220, 222
|
Rough-in | 11/22/2017 | 11/24/2017 | 11/23/2017 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Pressure Test | 11/22/2017 | 11/24/2017 | 11/23/2017 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Pressure Test | 11/22/2017 | 11/27/2017 | 11/22/2017 | A | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN Inspection cancelled from web by: GREGORY ANDERSEN
|
Rough-in | 11/22/2017 | 11/22/2017 | 11/22/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Framing around fire/smoke on 1st floor okay
|
Rough-in | 11/20/2017 | 11/21/2017 | 11/21/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Need to frame around fire/smoke damper per manufactures instructions
|
Rough-in | 11/15/2017 | 11/15/2017 | 11/15/2017 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN 107 - 112 okay
|
Rough-in | 11/6/2017 | 11/6/2017 | 11/6/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover bottom of tgi's and walls in units 116, 118, 216, 218, 316, 318, 416, 418.
|
Conference | 10/30/2017 | 10/30/2017 | 10/30/2017 | A | DONE |
Chad Schwendiman
|
|
|
Phone ###-#### - Spoke with Rob about Dryer duct terminations
|
Rough-in | 10/25/2017 | 10/25/2017 | 10/25/2017 | P | PASS |
Chad Schwendiman
|
|
|
4th floor rough-in please Phone #: ###-#### Inspection requested via web by GREGORY - okay to cover bottom of TGI's in units 407, 408, 409, 410, 411, 412, 414
|
Rough-in | 10/9/2017 | 10/9/2017 | 10/9/2017 | P | PASS |
Ben Livingston
|
|
|
3rd floor Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN prerock rooms 307,-314
|
Rough-in | 10/2/2017 | 10/3/2017 | 10/3/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - okay to cover bottom of TGI's in units 207-212, & 214
|
Rough-in | 9/27/2017 | 9/28/2017 | 9/28/2017 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Okay to cover the bottom of the TGI's in units 111, 112, 114, 109, 110, 107, 108.
|
Conference | 8/2/2017 | 8/4/2017 | 8/4/2017 | A | DONE |
Chad Schwendiman
|
|
|
Rob Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|