Permit Information
Permit NumberMEC17-05520
StatusFinaled
Name ECONO AIR
Site Address 1325 S LONGMONT AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: install complete hvac work in new construction home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/1/201810/2/201810/2/2018PPASS
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Joseph Profitt
Final9/18/20189/18/20189/18/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Joseph Profitt- range hood ducting ok- other corrections still need made
Final9/4/20189/5/20189/5/2018AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Joseph Profitt-
- range vent cant be flex needs to be smooth ducting- lineset penetration needs sealed- A/C breaker size needs to be a 15amp- couldnt find duct blast sticker
Rough-in12/14/201712/18/201712/18/2017PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Joseph Profitt
Rough-in12/13/201712/14/201712/14/2017AFAIL
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Joseph Profitt-Need 1" clearance around single wall vent. Insulation sheild needs 1" clearance around single wall vent. Need transfer grills in bedrooms. Fresh air needs to come off retutn air plenum. Per manual-j supply register needs to be in bath not walk-in closet.
Pressure Test12/13/201712/14/201712/14/2017APASS
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by Joseph Profitt-20 lb gas test pass