Permit Information
Permit NumberMEC17-05533
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 3714 W HILLCREST DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/13/20186/14/20186/14/2018APASS
DetailsJack Reynolds
Blast Witness at 9AM Logan will be there to let you in the home:) thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- Man J ok- line set seal ok- duct blast ok
Final5/31/20186/1/20186/1/2018PFAIL
DetailsJack Reynolds
AC: 1406 Phone #: ###-#### Inspection requested via web by Gary Reeves- condensate drain for upstairs unit is missing- need a duct blast report on upstairs unit- need updated Man J for upstairs unit- lineset penetration on west side needs sealed
Final4/20/20184/23/20184/23/2018PFAIL
DetailsChad Schwendiman
AC:7354 Phone #: ###-#### Inspection requested via web by Gary Reeves - No air balance reports on site, need duct blast on upstairs furnace, Need to complete combustion air piping for down stairs furnace, need combustion air for upstairs furnace and water heater
Rough-in1/25/20181/25/20181/25/2018PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves
Rough-in1/24/20181/24/20181/24/2018PFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - Supply run outs in master bath and wic don't match the manual J. Need to remove spray foam from around fireplace vent.
Pressure Test1/16/20181/17/20181/17/2018PPASS
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Gary Reeves
Rough-in1/16/20181/17/20181/17/2018PFAIL
DetailsTroy James
Phone #: ###-#### Inspection requested via web by Gary Reeves
Need to provide manual j report that matches what and how it was installed on site
Pressure Test1/15/20181/16/20181/16/2018APART
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - 20lb gas pass, 5lb flue pass for upstairs units, Need to pressure test water heater flue. basement furnace flue pressure test fail.
Rough-in1/15/20181/16/20181/16/2018AFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - Need approved Manaul J onsite. Need to pressure test water heater flue. basement furnace flue pressure test fail.