Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-02476
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 3030 S OWYHEE ST
Project NameBldg 2
Customer Number 
ePlanReviewNo
Description
New: complete HVAC Install - as per Katie no dryer exhausts in any of the apt's for this permit, just furnace, A/C & bath fans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/201810/10/201810/10/2018APASS
DetailsJack Reynolds
Duct blast witness a 8am, thanks 101-102-201-202-301-302 Phone #: ###-#### Inspection requested via web by Gary Reeves- units 01&02 duct blast ok- final ok- signed card for permanent occupancy
Final9/26/20189/28/20189/28/2018APART
DetailsJack Reynolds
duct blast tests at 8 thanks 103,104,203,204,303,304 Phone #: ###-#### Inspection requested via web by Gary Reeves
-03/04 final ok signed card for 03/04 occupancy
Final9/21/20189/21/20189/21/2018PPART
DetailsJack Reynolds
105,106,205,206,305,306 Phone #: ###-#### Inspection requested via web by Gary Reeves
- corrections on 05/06 ok- occupancy of 05/06 units ok
Final9/18/20189/18/20189/18/2018PFAIL
DetailsJack Reynolds
105,106,205,206,305,306 Phone #: ###-#### Inspection requested via web by Gary Reeves- all duct blasts ok- 106 has a hole in the return duct work that needs sealed- back draft damper outside is broken- 205- lineset insulation needs fixed and a transfer grille is missing- 206 lineset insulation needs fixed- 305 lineset insulation needs fixed-
Final9/17/20189/18/20189/18/2018ACANC
DetailsJack Reynolds
105,106,205,206,305,306 Phone #: ###-#### Inspection requested via web by Gary Reeves
- rescheduled for PM
Final9/5/20189/6/20189/7/2018APART
DetailsJack Reynolds
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
- duct blast on 107,108,307,308 ok- air balance on all ok- line sets need a little work outdoors
(support)- 307 needs a pan switch
- occupancy ok on 107,108,207,208,307,308
Final9/4/20189/5/20189/5/2018ACANC
DetailsJack Reynolds
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
- rescheduled ductblast and finals
Rough-in7/30/20187/31/20187/31/2018APART
DetailsJack Reynolds
Please Re-inspect 104-204-303-304 . thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Rough-in7/27/20187/30/20187/30/2018AFAIL
DetailsJack Reynolds
please inspect 103,104,203,204,303,304 Phone #: ###-#### Inspection requested via web by Gary Reeves
104- duct seal on return at furnace
204- supply flex being smashed in mech room- return pipe needs sealed at end cap- supply duct needs sealed at end cap
303- supply flex run needs fixed its being smashed - return end cap also needs to be sealed
304- supply run into living room needs support strap adjusted as to not smash flex
Rough-in7/25/20187/26/20187/26/2018APART
DetailsJack Reynolds
Please Inspect: 101,102,201,203,301,302
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Rough-in7/24/20187/25/20187/25/2018PFAIL
DetailsJack Reynolds
please inspect: 101,102,201,202,301,302 Phone #: ###-#### Inspection requested via web by Gary Reeves- 101 flex ducting needs strapped up/ supported
-201 lineset needs supported -flex runs are being smashed by framing- flex runs need supported/ strapped up
-202 flex runs need supported/ strapped up- some flex runs have large sags in them
-302 a few flex runs are being smashed by their supports
Rough-in7/24/20187/25/20187/24/2018ACANC
DetailsJack Reynolds
please Inspect 101,102,201 202, 301,302 Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Rough-in7/11/20187/12/20187/12/2018APART
DetailsJack Reynolds
Please Inspect 105,106,205,206,305,306 Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Rough-in7/11/20187/12/20187/11/2018PCANC
DetailsJack Reynolds
Please Inspect: 105,106,205,206,305,306 Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Rough-in7/11/20187/11/20187/11/2018PCANC
DetailsJack Reynolds
please inspect: 105,106,205,206,305,306 Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Rough-in7/10/20187/10/20187/10/2018PNR
DetailsJack Reynolds
105and 106 crawl not ready- some flex runs need supported- flex duct being smashed- line set insulation needs repaired and needs nail plates at floor-205 and 206 one lineset needs fire caulked at floor- some duct sealing needs finished- duct work is being smashed by ceiling and some flex runs need support- 305 and 306 flex duct needs rerouted and supports need adjusted flex ducting should be ran free or kinks or smashes and free flowing bends
Rough-in7/9/20187/10/20187/10/2018PCANC
DetailsJack Reynolds
please inspect 105,106,205,206,305 and 306 Phone #: ###-#### Inspection requested via web by Gary Reeves-
Rough-in6/28/20186/29/20186/29/2018APASS
DetailsJack Reynolds
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves- this included the dryer vents- R/I ok
Rough-in6/28/20186/28/20186/28/2018PFAIL
DetailsJack Reynolds
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
107- return needs sealed- linesets down wall need to be repaired and tape
108- linesets need to be repaired and taped
207- supply tap needs more duct seal- 4" run into walk-in closet is sagging and needs support- supply trunk in bathroom is being kinked by the ceiling framing
208- linesets need repaired and taped- supply run in hallway is kinked reposition support- liquid line on line set is touching the metal framing studs
307- supply run into dinning room has a large sag
308- supply run into the master room has a kink reposition support- supply run into bedroom 2 has a kink reposition support
Rough-in6/26/20186/27/20186/27/2018PFAIL
DetailsJack Reynolds
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
-107&108 need framing around ducts- need to fix all lineset insulation- 107 needs some duct sealing finished- 207&208 are not ready worker was still working on finishing boots- lineset insulation needs rips fixed- 307&308 needs lineset supported every 6'- also needs insulation fixed- every floor has work to still be done go through all units check work and when framing is done downstairs call in for R/I inspection