Permit NumberMEC18-02864
StatusFinaled
Name TVR INC
Site Address 1325 S VISTA AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Provide and Install 8 each RUUD Split Systems with accessories as per plans
Provide and Install 10 each Soler and Palau ceiling exhaust fans with accessories as per plans
Provide and Install 60 Tuttle and Bailey grilles, registers and diffusers as p
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/29/20188/30/20188/30/2018APASS
DetailsJack Reynolds
final - call travis
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- access doors ok- dryer vent ok- final ok signed card
Final8/27/20188/27/20188/27/2018PPART
DetailsJack Reynolds
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- lineset penetrations ok- lineset support ok- condensates ok- still need a few more access doors in hard lid ceiling and labeling on all doors
Final8/24/20188/24/20188/24/2018PNR
DetailsJack Reynolds
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- not ready
Rough-in8/23/20188/24/20188/24/2018APASS
DetailsJack Reynolds
flue re-inspect Phone #: ###-#### Inspection requested via web by Brandon Sorensen
- unit number 7 5 lb flue test ok
-still need to see condensates done by others
- need to see hard lid access doors by others
- line sets on roof need supports and line set penentrations need sealed on roof
- all this for a final
Rough-in8/22/20188/23/20188/23/2018APART
DetailsJack Reynolds
pressure test flues Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 7 out of the 8 5lb flue test passed- unit number 7 couldnt hold 5lb- primary and secoundary condensates drains still need ran- need to see access doors installed in hard lid ceiling with labels at final- fire damper clearances to sheet rock ok
Rough-in8/17/20188/20/20188/20/2018APASS
DetailsJack Reynolds
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok- ok for cover
Final8/16/20188/16/20188/16/2018PCANC
DetailsJack Reynolds
pressure test for flue and final - call travis Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen Inspection cancelled from web by: Brandon Sorensen
Rough-in7/23/20187/23/20187/23/2018PPART
DetailsJack Reynolds
cover inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- fire/smoke dampers installed ok- access openings for balance dampers ok- fresh air ducting and supply runs still need insulation- a few locations still need duct seal finished
Rough-in6/19/20186/21/20186/21/2018AFAIL
DetailsChad Schwendiman
rough in - call Travis Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Need framing around all 4 sides of fire/smoke dampers per installation instructions, Need access door framing in for balance dampers, need to insulate supply and return duct work above hard lids