Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-03151
StatusFinaled
Name DEBEST PLUMBING INC
Site Address 7607 W GRATZ DR
Project NameLyle Pearson Mercedes Remodel
Customer Number18-54
ePlanReviewNo
Description
Alteration: gas piping to RTU & Fireplace
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/3/20194/3/20194/3/2019PPASS
DetailsBrian Scoles
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- final ok- no card onsite to sign
Card not on site to sign4/3/20194/3/20194/3/2019PPASS
DetailsBrian Scoles
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
Final4/2/20194/2/20194/2/2019PPART
DetailsBrian Scoles
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- roof gas piping ok- fireplace piping needs to be hard piped or csst gas piping with sleeve thru appliance- appliance connectors can not penetrate thru appliance- recall in when ready went over with Omar onsite- IFGC 411.3.3
Mec-Aging Inspection3/25/20193/25/20193/25/2019 PASS
DetailsBrian Scoles
WIP-
Pressure Test9/24/20189/24/20189/24/2018PPASS
DetailsJack Reynolds
Gas Line - Pressure Test. If questions call Omar @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- 60lb gas pressure test on the roof ok
Pressure Test9/14/20189/14/20189/14/2018PPASS
DetailsBrian Scoles
if questions call Omar @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- 20lb gas pass to fireplace
Pressure Test7/5/20187/6/20187/6/2018PPASS
DetailsJack Reynolds
If questions contact Jerry Prough @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- 20 lb gas pressure test ok
Pressure Test7/3/20187/5/20187/5/2018AFAIL
DetailsBrian Scoles
if questions call Jerry @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- gauge at fireplace below 20psi- tried to call Jerry no answer