Permit Information
Permit NumberMEC18-04702
StatusFinaled
Name YMC INC
Site Address 4455 E WARM SPRINGS AVE
Project Name 
Customer Number2107351
ePlanReviewNo
Description
New: HVAC, duct, gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/17/20194/18/20194/18/2019APASS
DetailsBen Livingston
Please Call Bryan at least one hour before inspection. Thank you so much!
Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Final4/9/20194/11/20194/11/2019AFAIL
DetailsChad Schwendiman
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
1) Need to label all fire damper access doors
2) Need to finish glueing and support condensate piping
3) Need UV protection on aramflex outdoors
4) Need to angle around fire damper openings in rated ceilings
5) Need to install missing exhaust fan grill
6) Need to extend dryer ducts outside of the wall
7) Need air balance report
8) Need to install A/C that was removed
9) Need letter from engineer for room usage change and removal of exhaust fan in oxygen storage
Rough-in3/26/20193/28/20193/28/2019PPASS
DetailsBen Livingston
Please call Don, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
above grid okay all rooms
Pressure Test3/20/20193/20/20193/20/2019PCANC
DetailsEric Strole
Please call Mike, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Rough-in2/21/20192/22/20192/22/2019APASS
DetailsEric Strole
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-area B pass.
Rough-in2/20/20192/21/20192/21/2019PPART
DetailsEric Strole
Please call Bryan, thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Area B duct seal ok. Need to fire caulk all ducts going thru all fire rated walls.
Rough-in2/13/20192/13/20192/13/2019PPASS
DetailsJack Reynolds
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- area B caffateria and theater and corridor soffits with duct work ok for cover duct seal ok
Rough-in2/11/20192/11/20192/11/2019PFAIL
DetailsJack Reynolds
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- not ready area B sofits- return sleeve needs finished one supply linear can needs finished in theater room and duct sealed
- found a few location that needed duct seal finished
- two fuseable link dampers are possibly being moved out of fire rating. damper needs to stay in rated assembly. smaller duct will most likely need access doors to access fuseable link
Rough-in1/11/20191/14/20191/14/2019APASS
DetailsJack Reynolds
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 6 fire dampers in area B framing clearances and dry wall ok
- 2 linesets R/I ok
Rough-in12/17/201812/18/201812/18/2018APASS
DetailsChad Schwendiman
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to sheetrock area c okay to insulate duct in joist space in area b
Rough-in12/11/201812/11/201812/11/2018PPASS
DetailsChad Schwendiman
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to sheetrock area D
Rough-in12/7/201812/10/201812/10/2018AFAIL
DetailsChad Schwendiman
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need to install retaining angles on fire dampers per instructions
Pressure Test12/5/201812/5/201812/5/2018PPASS
DetailsJack Reynolds
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 60lb gas pressure test on building b,c,d ok
- talked with dave about making sure to support gas piping per specs through out building
Pressure Test12/4/201812/4/201812/4/2018PFAIL
DetailsChad Schwendiman
Please call Dave, Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - not holding pressure
Rough-in11/30/201812/3/201812/3/2018APART
DetailsChad Schwendiman
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to insulate duct in area D, exhaust fans in area D okay. Okay to sheet rock ceiling in west area
Rough-in11/29/201811/30/201811/30/2018AFAIL
DetailsChad Schwendiman
Please call Bryan ###-####. thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need fire/smoke damper installaion instructions to verify expansion clearances
Pressure Test11/27/201811/27/201811/27/2018PPASS
DetailsChad Schwendiman
Call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 60lb gas pass for temp heat
Rough-in11/7/201811/8/201811/8/2018APART
DetailsChad Schwendiman
We need a R/I for Area A, please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to cover ceilings in area A except for around fire dampers in the hallway
Rough-in10/29/201810/29/201810/29/2018PCANC
DetailsBen Livingston
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
called under wrong permit
Rough-in10/25/201810/26/201810/26/2018APART
DetailsEric Strole
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Area A, C & D corridor overhead duct seal pass. OK to insulate.
Pressure Test10/19/201810/19/201810/19/2018PPART
DetailsEric Strole
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-20 lb gas test on 3/4 line from area B to furnace in area A pass.
Pressure Test10/18/201810/18/201810/18/2018PFAIL
DetailsEric Strole
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-gas test fail.
Conference10/15/201810/16/201810/16/2018PPASS
DetailsBen Livingston
1pm
Pressure Test10/16/201810/16/201810/16/2018PNR
DetailsEric Strole
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Not ready.
Conference10/15/201810/16/201810/16/2018PDONE
DetailsEric Strole
Please call Bryan ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Conferance on fire/smoke dampers.
Pressure Test10/15/201810/16/201810/16/2018AFAIL
DetailsEric Strole
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Gauge will not zero out & 1/2" csst at 160' is undersized.
Conference10/15/201810/15/201810/15/2018PCANC
DetailsBen Livingston
Please call Bryan ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum