Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberMEC18-05856
StatusFinaled
Name DIAMOND HEATING AND COOLING
Site Address 5920 W MARVIN ST
Project Name 
Customer Number16068351
ePlanReviewNo
Description
Alteration or Repair: REPLACEMENT OF EXISTING FURNACE AND AC COIL AND ALSO REPLACING MAJORITY OF THE DUCT WORK. MAN J AND D WILL BE PROVIDED ONSITE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/7/20193/8/20193/8/2019APASS
DetailsBrian Scoles
ready for final inspection- stamped approved man j will be onsite and my guys will be there in the AM from 9-11a to meet you. Please call Sam my lead installer when in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- final ok
Rough-in12/12/201812/14/201812/14/2018PPART
DetailsBrian Scoles
PLEASE CALL OUR INSTALL MANAGER TODD 30-45 MINS BEFORE ARRIVAL, SO HE CAN MEET YOU THERE AND ALLOW ACCESS Phone #: ###-#### Inspection requested via web by Rick Montgomery- R/I ok- need to submit manual J to city and get approved- needs fresh air installed to R/A plenum- have issues resolved by final
Rough-in12/6/201812/7/201812/7/2018PFAIL
DetailsBrian Scoles
PLEASE CALL HOMEOWNER TIM WHEN 30-45 MINS IN ROUTE SO HE CAN MEET YOU THERE. THANKS SO MUCH AND HAPPY FRIDAY! Phone #: ###-#### Inspection requested via web by Rick Montgomery- need approved manual J onsite- need to seal all boots to floor with mastic- need to run combustion air from furnace thru roof garage is to small- toe kicks need to be all ducted no wood can be exposed on floor and wood framed in around pipe on floor- register in bath room not completed