Permit Information
Permit NumberMEC19-00050
StatusFinaled
Name ARCTIC AIR INC
Site Address 1693 S FEDERAL WAY
Project NameApt 101, 102, 103, 104
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Replace furnaces and A/C's in all 4 units - apts 101, 102, 103, 104
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/4/20192/5/20192/5/2019PPASS
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- final ok
Final2/4/20192/5/20192/4/2019ACANC
DetailsJack Reynolds
>> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
Final2/1/20192/4/20192/4/2019APART
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- upstairs units had access- need to finish filling out duct blast stickers upstairs- still need access to units downstairs- dyrer vent done by other needs finished
Conference1/31/20192/1/20192/1/2019APASS
DetailsJack Reynolds
Duct Blast 9:30
Shane ###-#### Inspection requested via web by Konrad Swartz
- all units duct blast ok
Rough-in1/24/20191/25/20191/25/2019APASS
DetailsJack Reynolds
Rough in and Duct Blast 9:30 Inspection requested via web by Konrad Swartz
- R/I ok
-unit 103 duct blast ok
- air balance will be ready to check for final
Rough-in1/23/20191/23/20191/23/2019PPART
DetailsJack Reynolds
Inspection requested via web by Konrad Swartz
- Man J needs to be stamped by the city and onsite
- range hood vent needs to be smooth walled pipe
- one dryer vent needs new back draft damper installed
- one unit has line set insulation that needs fixed
Final1/14/20191/16/20191/16/2019ACANC
DetailsJack Reynolds
The Builder and Property Manager are requesting 8:30 to 10:30 AM as these are occupied >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
Final1/8/20191/9/20191/9/2019PFAIL
DetailsJack Reynolds
Property manager is requesting 3pm he will be onsite Inspection requested via web by Konrad Swartz
- need man J stamped and approved onsite
- need to add bathroom exhaust fan and duct work to permit
- lineset need UV protection
- condensate line need extended down to the ground from the 2nd floor