Permit Information
Permit NumberMEC19-01612
StatusFinaled
Name PRECISION HEATING & A/C
Site Address 10487 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Hvac
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/5/20196/6/20196/6/2019APASS
DetailsBrian Scoles
Rob Phone #: ###-####- final ok- signed occupancy card
Rough-in5/31/20195/31/20195/31/2019PPASS
DetailsBrian Scoles
fire damper inspection- fire damper clearances ok-angles ok- still need all firecaulking removed- Temp occupancy ok- call in final when registers have been installed on fire dampers and fire caulk is removed
Conference5/30/20195/31/20195/31/2019ADONE
DetailsBrian Scoles
Rob Phone #: ###-####- discussed fire dampers and looked at angles- reschedule for R/I in after noon- went over installation instructions with contractor onsite
Rough-in5/15/20195/16/20195/16/2019AFAIL
DetailsBrian Scoles
re-inspect // Rob Phone #: ###-####- need top complete framing around firedampers installed- will need to add return to RTU C5- talked with engineer about issue with return to that RTU- need to submit new plan mod to city for approval and have issued version of print onsite to do inspection next time
Rough-in5/9/20195/10/20195/10/2019PPART
DetailsBrian Scoles
Rob- please call for access Phone #: ###-####- 3 supply fire dampers clearances ok- need to remove all fire caulking- need to run return air per prints and instsll fire dampers or get engineer approval of system installed- seal on exhaust duct ok- ok to cover
Final5/7/20195/7/20195/7/2019PNR
DetailsChad Schwendiman
Rob Phone #: ###-####
Rough-in5/7/20195/7/20195/7/2019PFAIL
DetailsChad Schwendiman
Rob Phone #: ###-#### - Need to seal exhaust duct. need access to roof, Need to install sleeves ob fire dampers that comply with the manufactures instructions, Need to install retaining angles per instructions on fire dampers after sheetrock is complete. need to install duct mounted access doors for fire dampers.