Final | 11/7/2019 | 11/7/2019 | 11/7/2019 | P | PASS |
Brian Scoles
|
|
|
Call Dwight Van Hees for access if needed at ###-#### or Jeff Creek ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek- final ok
|
Final | 10/31/2019 | 11/1/2019 | 11/1/2019 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- per phone call with Jeff- missing air balance- will reschedule
|
Final | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek 1- need locking caps on both a/c service ports 2- need airbalance report for both units onsite none found 3- need sediment trap between gas shut off valve and furnace both units 4-water heater flue in laundry room needs 6" clearance to single wall pipe from sheetrock or install b vent 5- missing R/A grill 2nd floor hallway
|
Rough-in | 7/15/2019 | 7/16/2019 | 7/16/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- R/I ok- will need gable vents installed by final for combustion air from attic- need resubmitted man j onsite and approved by city at final with correct furnace installed south furnace doesnt match man j
|
Pressure Test | 7/15/2019 | 7/16/2019 | 7/15/2019 | P | CANC |
Brian Scoles
|
|
|
Jeff Phone #: ###-#### Inspection cancelled from web by: Andrea Creek
|
Rough-in | 7/12/2019 | 7/15/2019 | 7/15/2019 | P | CANC |
Brian Scoles
|
|
|
Thanks, Jeff Creek. Phone #: ###-#### >> Inspection requested via web by Andrea Creek
|
Rough-in | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | FAIL |
Brian Scoles
|
|
|
We need both 60lb an 20lb pressure tests please. If any questions please call Jeff Creek at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek 1- need to seal all supply and retun air registers- 2- supply duct in garage joists is below joists and insulated to r8 3- fresh air can not come from register can needs to be from plenum 4- b vent in garage at ceiling needs 1" clearance to wood and attic needs draft stop installed and firecaulked 5- house needs 2 gable end vents in attic to draw combustion air from attic for laundry room 6- framing needs completed around supply/return and b vent chase and draft stop installed around supply and return ducting 7- need fresh air to upstairs downstairs unit didnt see any 8- need nail plate on dryer duct at ceiling 9- south furnace model # does not match man j need to submit whats installed 10- R/A panning in garage needsremoved and ran in pipe and insulated to r6 unconditioned space- left notice front window
|
Pressure Test | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | PASS |
Brian Scoles
|
|
|
We need both 60lb an 20lb pressure tests please. If any questions please call Jeff Creek at ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek- 60lb gas pass tagged meter- 20lb gas pass- 5lb flue pass
|