Permit Information
Permit NumberMEC19-02910
StatusIssued
Name SUTTON GREGORY L
Site Address 211 N BACON DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Addition: 3 station mini split and two bath fans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Mec-Aging Inspection7/7/20207/7/20207/7/2020 CANC
DetailsBen Livingston
wip
Mec-Aging Inspection4/7/20204/7/20204/7/2020 CANC
DetailsBen Livingston
wip
Final1/7/20201/7/20201/7/2020AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Greg Sutton
3- condensate line needs supported on outside of house/ penetrations need sealed
- line sets need insulation finished/ UV protection installed and penetration needs sealed
- outdoor HP needs 3" pop ups
Conference7/11/20197/11/20197/11/2019AFAIL
DetailsBen Livingston
Mini split rough in correction and bathroom vent correction
Late morning if possible Phone #: ###-#### Inspection requested via web by Greg Sutton
---still need to add exhaust fans to permit---
Rough-in7/11/20197/11/20197/11/2019PPASS
DetailsBen Livingston
Mini split rough in correction and bathroom vent correction
Late morning if possible Phone #: ###-#### Inspection requested via web by Greg Sutton
Rough-in7/10/20197/10/20197/10/2019PFAIL
DetailsBen Livingston
2nd floor rough in mini splits Phone #: ###-#### Inspection requested via web by Greg Sutton
--condensate piping not approved material, need 3/4" pvc.
-- exhaust duct needs 6" roof jack not 4".
-- exhaust duct needs hangers.
-- on final energy star fan needs correct timer for ventalation.
-- need to add exhaust fans to permit