Permit Information
Permit NumberMEC19-03096
StatusFinaled
Name YMC INC
Site Address 2909 W ELDER ST
Project Name 
Customer Number2107841
ePlanReviewNo
Description
Addition: PTAC units, exhaust fans, one split system, and duct work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/16/20203/16/20203/16/2020PPASS
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you!! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- final ok
- occ card signed
Final3/11/20203/12/20203/12/2020ACANC
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- check R/I inspection from the afternoon of
3-11-20 for correction notice
Rough-in3/11/20203/11/20203/11/2020PFAIL
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- should have been a final not a R/I
- A/C's need locking caps installed on service ports
- line set penetrations need sealed and line set insulation needs UV protections
- all fire damper access doors need installed and all dampers need labeled
- commerical dryers need 2" min clearances to combustibles and insulation sheild installed in wall
- dryers vent length is too long on both dryers
- damper interlock with dryers needs adjusted
Rough-in2/25/20202/26/20202/26/2020APASS
DetailsJack Reynolds
1st floor Men''s and Women''s restrooms. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested
via web by Rhonda Marcum
- 2 bathrooms 1st floor R/I ok
Rough-in2/20/20202/20/20202/20/2020PFAIL
DetailsJack Reynolds
Rough-in on men''s and women''s bathroom, final on 2nd, 3rd, and 4th floor if possible. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- plan mod is under review
Rough-in1/28/20201/30/20201/30/2020APASS
DetailsBrian Scoles
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum- lobby and hallway ok- 2 fire damper angles ok- access on duct and ceiling ok- duct insulation installed 2 locations- ok for cover
Rough-in1/27/20201/28/20201/28/2020PFAIL
DetailsJack Reynolds
Rough in for first floor lobby and hallways, please call Bryan at least 30 in prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- hard lid cover in lobby and hallway 1st floor fail
- fire dampers missing retaining angles
- fire damper in duct access door needs moved for access from ceiling
- two locations of duct insulation need installed
Conference1/7/20201/8/20201/8/2020APASS
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Rough-in1/8/20201/8/20201/8/2020APART
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
2- 8" F/S damper clearances ok
all bathroom hard lids ok for cover other than two guest bathrooms in the corridor next to gym.
- talked with HVAC contractor and general about fire dampers in ceiling/floor assembly per approved drawnings. Contractor says they will not be able to fit a fire damper in ceiling space. Explained that they will need to have this issue looked at by design professional and then reviewed by city before moving foward.
Rough-in12/20/201912/23/201912/23/2019AFAIL
DetailsJack Reynolds
Please call Bryan at least 30 min prior to inspection, thank you, Merry Christmas! Phone #: ###-#### Inspection requested via web by Rhonda Marcum

- duct seal ok for insulation
- two 8" F/S dampers need proper clearances
- two exhaust fans penetrating ceiling/floor assembly need dampers and access doors installed
- two exhaust flues for commerical dryers not installed yet
Rough-in10/15/201910/16/201910/16/2019APART
DetailsJack Reynolds
2nd, 3rd,; 4th floor exhaust rough in. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- 2nd/3rd/4th floor exhaust ducting R/I ok
Rough-in10/3/201910/3/201910/3/2019PFAIL
DetailsJack Reynolds
2nd ; 3rd floor exhaust fans, 4th floor radiant dampers. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- exhaust fans are not installed per prints on 2nd, 3rd and 4th floor
Rough-in7/30/20198/1/20198/1/2019APASS
DetailsJack Reynolds
Please call Delroy at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
3- 5lb flue pressure test for water heater ok
1- 5lb flue pressure test for furnace ok
- line sets on 1st floor ok