Permit Information
Permit NumberMEC19-03211
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 1870 S KIMBALL PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Complete HVAC install
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/4/201912/4/201912/4/2019PPASS
DetailsBrian Scoles
AC: 4141 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
Final12/3/201912/3/201912/3/2019PFAIL
DetailsBrian Scoles
AC:4141 Phone #: ###-#### Inspection requested via web by Gary Reeves- no corrections made
Final11/27/201912/2/201912/2/2019PFAIL
DetailsBrian Scoles
AC: 4141 Phone #: ###-#### Inspection requested via web by Gary Reeves- R/A and outside air need R-6 insulation and maintain 75% actual value- need to seal lineset penetration at condenser location- gas stub out for future fire pit needs hooked up to anodised riser with shutoff valve and all piping inert taped
Rough-in9/3/20199/3/20199/3/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves
Pressure Test8/29/20198/30/20198/30/2019PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - 20lb gas, 5lb flue
Rough-in8/29/20198/30/20198/30/2019PFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Gary Reeves - Need to insulate supply duct Y in attic on 2nd floor, Need to remove kink in exhaust flex duct on bath fan on 2nd floor, Missing return transfer in study
Pressure Test7/23/20197/24/20197/24/2019APART
DetailsBrian Scoles
Please inspect under ground gasline Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass underground only- ok to backfill