Permit Information
Permit NumberMEC19-03652
StatusFinaled
Name TVR INC
Site Address 350 N MILWAUKEE ST Unit: 2016
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Remove and relocate existing type 1 kitchen hood
Provide and install new welded liquid tight grease duct as necessary
Light test on grease duct
Provide and install new fire wrap for grease duct as necessary
Relocate existing grilles
Assembly and s
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/14/201910/14/201910/14/2019PPASS
DetailsBrian Scoles
final - call luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok- card signed- air balance for pizza oven ok however if change of occupancy occurs again, class 1 hood will have to go to original CFM quanities if cook line changes from pizza oven- Original cfm was 3500 for both class 1 hood and MAU unit
Final10/3/201910/4/201910/4/2019APART
DetailsBrian Scoles
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need air balance report onsite per existing hood cfm that was emailed to Luke for exhaust and MAU- need to install 1500 degree gasket on curb- temp occupancy ok
Rough-in9/27/20199/30/20199/30/2019APASS
DetailsBrian Scoles
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok
Rough-in9/3/20199/3/20199/3/2019PPASS
DetailsBrian Scoles
light test - call Luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- light test pass- ok for 1st and 2nd layer fire wrap
Conference8/26/20198/27/20198/27/2019ADONE
DetailsBrian Scoles
consult with Luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- went over class 1 hood- since no labeling can be found on ul listed hood by captive aire will install to 2012 IMC-
Conference8/26/20198/27/20198/27/2019ADONE
DetailsChad Schwendiman
meet at mall- will call u in morning with time - Meet onsite to look at exhisting class 1 hood. Exhisting hood was UL listed but all the writing on the tags is gone at this point. Hood will need to meet 18" clearances per code since previous clearance information is unknown.