Final | 10/4/2019 | 10/4/2019 | 10/4/2019 | P | PASS |
Jack Reynolds
|
|
|
repairs/changes made listed on failed inspection. Thank you Phone #: ###-#### Inspection requested via web by jeremy wanders - furnace ac coil co ok
|
Final | 10/2/2019 | 10/3/2019 | 10/3/2019 | A | FAIL |
Jack Reynolds
|
|
|
Replace existing furnace with a new furnace. Added a air conditioner. Phone #: ###-#### Inspection requested via web by jeremy wanders - need locking caps on A/C service ports - need to seal line set penetration - electrical wiring to furnace is touching b vent and needs terminated properly at furnace -secondary drain needs a wet switch installed - vent piping from furnace needs slope with out dips and sags - natural draft needs to connect at highest point in common vent above fan assist appliance
|