Permit NumberMEC19-04908
StatusFinaled
Name ADVANCED HEATING & COOLING
Site Address 2246 W KOOTENAI ST
Project NameKootenai Townhomes - Bldg B
Customer Number 
ePlanReviewNo
Description
HVAC for entire New single family dwelling
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/21/20202/24/20202/24/2020APASS
DetailsJack Reynolds
Final Inspection. Please contact Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- final ok
Final2/10/20202/11/20202/11/2020PFAIL
DetailsJack Reynolds
Requesting Final Inspection - Please contact Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- need air balance reports/ duct blast sticker needs completed
- line set penetration needs sealed to roof
Final2/4/20202/7/20202/7/2020PNR
DetailsJack Reynolds
Requesting a final for Friday the 7th pm, Please call Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- talking with Robbie condensate lines are not complete and air balances are not finished.
Rough-in11/13/201911/13/201911/13/2019PPASS
DetailsJack Reynolds
Requesting an inspection for Wednesday. Please contact Mark prior to coming out. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- end unit R/I ok outside air ok
- condensates still need ran
Rough-in11/1/201911/1/201911/1/2019PPART
DetailsJack Reynolds
Requesting Cover Inspection. Please contact Mark prior to coming out. ###-####. Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- partial R/I for pre rock ok on end unit only
- exhaust fan termination 1st floor will terminate side of building on end units and a soffit will be built for center units to terminate between door and window
- talked with contractor and builder about condensates for cooling coils and where they will drain. RFI being built for condensates
Rough-in10/30/201910/31/201910/31/2019AFAIL
DetailsJack Reynolds
Cover Inspection for Building B Unit 3. Please contact Mark Prior to coming out. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator

- duct seal ok on middle unit
- exhaust termination on 1st floor is within 3' of window and front door of next unit