Final | 2/21/2020 | 2/24/2020 | 2/24/2020 | A | PASS |
Jack Reynolds
|
|
|
Final Inspection. Please contact Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - final ok
|
Final | 2/10/2020 | 2/11/2020 | 2/11/2020 | P | FAIL |
Jack Reynolds
|
|
|
Requesting Final Inspection - Please contact Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - need air balance reports/ duct blast sticker needs completed - line set penetration needs sealed to roof
|
Final | 2/4/2020 | 2/7/2020 | 2/7/2020 | P | NR |
Jack Reynolds
|
|
|
Requesting a final for Friday the 7th pm, Please call Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - talking with Robbie condensate lines are not complete and air balances are not finished.
|
Rough-in | 11/13/2019 | 11/13/2019 | 11/13/2019 | P | PASS |
Jack Reynolds
|
|
|
Requesting an inspection for Wednesday. Please contact Mark prior to coming out. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator - end unit R/I ok outside air ok - condensates still need ran
|
Rough-in | 11/1/2019 | 11/1/2019 | 11/1/2019 | P | PART |
Jack Reynolds
|
|
|
Requesting Cover Inspection. Please contact Mark prior to coming out. ###-####. Phone #: ###-#### Inspection requested via web by Commercial Coordinator - partial R/I for pre rock ok on end unit only - exhaust fan termination 1st floor will terminate side of building on end units and a soffit will be built for center units to terminate between door and window - talked with contractor and builder about condensates for cooling coils and where they will drain. RFI being built for condensates
|
Rough-in | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | FAIL |
Jack Reynolds
|
|
|
Cover Inspection for Building B Unit 3. Please contact Mark Prior to coming out. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- duct seal ok on middle unit - exhaust termination on 1st floor is within 3' of window and front door of next unit
|