Permit Information
Permit NumberMEC19-05152
StatusFinaled
Name 1A HEATING AND COOLING
Site Address 4501 W KOOTENAI ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: New furnace and ac // Santiago called in to add a gas line (other), range vent (other) ,1 dryer exhaust, 3 exhaust fans 1and duct work 12-02-19 JCA
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/17/201912/18/201912/18/2019PPASS
DetailsJack Reynolds
call for access- Santiago Phone #: ###-####
- final ok
Final12/9/201912/10/201912/10/2019AFAIL
DetailsJack Reynolds
call for lock box code // Santiago Phone #: ###-####
- furnace needs electrical wiring finished
- dryer vent needs finished
- furnace flue and all work in attic has not been inspected. need access
Pressure Test12/9/201912/10/201912/10/2019APASS
DetailsJack Reynolds
call for lock box code // Santiago Phone #: ###-####
- 20lb gas pressure test ok
Final12/5/201912/6/201912/6/2019PNH
DetailsJack Reynolds
Santiago Phone #: ###-####
- called number in notes
- no access to house
Final11/13/201911/14/201911/14/2019AFAIL
DetailsJack Reynolds
Los box on front door code 208 Phone #: ###-#### Inspection requested via web by santiago ramirez

-condensate in crawl needs slope
- line set insulation at furnace needs repaired and supported in the crawl
- duct work between furnace and coil needs insulation installed
- duct work needs added to permit and inspected
- several exhaust fans need added to permit and inspected
- dryer vent needs added to permit
- range hood venting needs added to permit and smooth walled duct installed
- gas line to range needs added to permit and pressure tested
- A/C needs locking caps installed on service ports