Permit Information
Permit NumberMEC20-00086
StatusFinaled
Name ELITE SYSTEMS
Site Address 1990 S EAGLESON RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/23/20204/23/20204/23/2020PPASS
DetailsJack Reynolds
2583 is garage code Inspection requested via web by Loren Bailey
- final ok
Final4/22/20204/22/20204/22/2020PFAIL
DetailsJack Reynolds
Garage code 2583 Phone #: ###-#### Inspection requested via web by Loren Bailey
- line set insulation at outdoor unit needs repaired and UV protected
Pressure Test2/5/20202/6/20202/6/2020APASS
DetailsBrian Scoles
Pressure test for flue Phone #: ###-#### Inspection requested via web by Loren Bailey- 5lb flue pass
Rough-in2/3/20202/4/20202/4/2020APASS
DetailsJack Reynolds
Inspection requested via web by Loren Bailey
- flue test failed gauge under 5lb
will need to see 5lb witness at final or reschedule a 5lb flue test before final
- R/I ok
Rough-in1/30/20201/31/20201/31/2020AFAIL
DetailsBrian Scoles
Inspection requested via web by Loren Bailey- corrections not made
1- need to fix kink in lineset at crawl entrance and repair all arma flex in crawl exposed copper showing
2- need 1" clearance to sheet rock on w/h flue
3- range duct needs seal at roof and roof jack is off roof looking from outside
4- need to see flue test for witness

see notice front entry window

reinspection fee issued
Pressure Test1/31/20201/31/20201/31/2020AFAIL
DetailsBrian Scoles
Inspection requested via web by Loren Bailey- 20lb gas pass tagged meter location- need to see flue test per earlier notes
Rough-in1/30/20201/30/20201/30/2020PFAIL
DetailsBrian Scoles
Inspection requested via web by Loren Bailey- not all corrections are made- see notice front entry window
Pressure Test1/30/20201/30/20201/30/2020PFAIL
DetailsBrian Scoles
Inspection requested via web by Loren Bailey- gauge wont zero out on gas line
Rough-in1/29/20201/29/20201/29/2020PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Loren Bailey
- line set in crawl needs arma flex repaired and copper line fixed from being over bend
- 20 lb fail gauge under 20lb
- need to see a 5lb flue test
- b vent needs 1' clearances high and low
- range vent needs sealed near roof line
Pressure Test1/29/20201/29/20201/29/2020PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Loren Bailey
- 20lb gas pressure test fail gauge under 20lb
- need to see 5lb flue pressure test