Rough-in | 2/28/2020 | 2/28/2020 | 2/28/2020 | P | PASS |
Brian Scoles
|
|
|
Hazen Phone #: ###-####- r/i ok- ok to cover exterior chase- need to seal storm collar by final
|
Rough-in | 2/14/2020 | 2/18/2020 | 2/18/2020 | P | FAIL |
Brian Scoles
|
|
|
Sheldon Phone #: ###-####- need to remove siding around flue to check clearances to pipe- will need to insulate chase to R-8 per codes thats referenced
|
Rough-in | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | FAIL |
Ben Livingston
|
|
|
ROUGH IN ON EXTERIOR PIPE Phone #: ###-#### Inspection requested via web by Sheldon Lebow - building permit and inspected prior to cover - - still need BLD permit before MEC reinspection -
|
Rough-in | 1/17/2020 | 1/21/2020 | 1/21/2020 | A | PART |
Brian Scoles
|
|
|
PLEASE CALL SHELDON 1 HR BEFORE SO HE CAN MEET YOU OUT THERE. ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Lebow- fireplace R/I in living room only ok for cover- insulation shield verified in attic- need framing completed around b vent above roof and call in for inspection once framed and this will require a building permit and inspected prior to cover
|
Rough-in | 1/17/2020 | 1/17/2020 | 1/17/2020 | P | FAIL |
Brian Scoles
|
|
|
GARAGE CODE IS 1129. PLEASE KNOCK ON THE DOOR TO SEE IF HOMEOWNERS ARE HOME, IF NOT USE GARAGE CODE Phone #: ###-#### Inspection requested via web by Sheldon Lebow 1- need to secure csst gas piping behind fireplace laying against it 2- contractor needs to provide ladder to access attic to check clearances and insulation shield and roof to check clearances on b vent up exterior wall and may need supported cant verify from ground 3- need framing completed around exterior b vent per 2428.2.9 and this will require a building permit and have inspected
draft stop seal and metal ok above fireplace
|
Rough-in | 1/14/2020 | 1/15/2020 | 1/15/2020 | P | FAIL |
Brian Scoles
|
|
|
GARAGE CODE IS 1129. PLEASE KNOCK ON THE DOOR TO SEE IF HOMEOWNERS ARE HOME, IF NOT USE GARAGE CODE. Phone #: ###-#### Inspection requested via web by Sheldon Lebow 1- need gas piping stubbed into fireplace 2- metal firestop at ceiling in fireplace chase needs to cover hole completely and firecaulked around b vent 3- need ladder provided by contractor to access piping in attic to verify insulation shield 4- need b vent installation instructions for b vent onsite - piping ran exposed on outside of house above garage roof line needs to to meet G2428.2.9 of IRC or manufactures installation instruction stating b vent can be ran exposed
|
Rough-in | 1/10/2020 | 1/13/2020 | 1/13/2020 | A | NH |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Sheldon Lebow- no one home- no access
|