Final | 4/8/2020 | 4/8/2020 | 4/8/2020 | P | PASS |
Jack Reynolds
|
|
|
someone will be there to allow entry for the inspector. Call Damon @ ###-#### for any entry issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - final ok
|
Final | 4/3/2020 | 4/7/2020 | 4/7/2020 | A | PART |
Jack Reynolds
|
|
|
the door should be unlocked for inspector entry. If it''s not, please call Damon @ ###-#### for assistance. Phone #: ###-#### Inspection requested via web by Angie Maguire - partial final - 2lb gas line to patio needs gauge removed and cap installed
|
Rough-in | 1/17/2020 | 1/21/2020 | 1/21/2020 | A | PASS |
Jack Reynolds
|
|
|
Call Eric @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - R/I ok
|
Rough-in | 1/16/2020 | 1/17/2020 | 1/17/2020 | A | FAIL |
Jack Reynolds
|
|
|
Call Jason with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - dryer vent needs nail plate - two mini split heads need condensate ran in min 3/4" pvc
|
Pressure Test | 1/16/2020 | 1/17/2020 | 1/17/2020 | A | PASS |
Jack Reynolds
|
|
|
Call Jason with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - 20lb gas pressure test ok - tagged meter location
|