Permit NumberMEC20-00341
StatusFinaled
Name EVENFLO HEATING & AIR CONDITIONING
Site Address 9000 W MALAD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Install new fireplace. Install gasline to the range and fireplace. relocate Heatpump. Install dryer vent. replace return air duct.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/23/20203/23/20203/23/2020PPASS
DetailsBrian Scoles
Bj 5730755 Inspection requested via web by william kerwin- final ok
Final3/18/20203/19/20203/19/2020AFAIL
DetailsBrian Scoles
Bj 5730755. Code 7777 Inspection requested via web by william kerwin
1- range duct needs vented to outside
2- need locking caps on heat pump service ports
3- need to seal lineset penetration downstairs in closet to outside

talked to BJ by phone
Rough-in1/27/20201/27/20201/27/2020PPASS
DetailsBrian Scoles
Bj 2085730755 Inspection requested via web by william kerwin- R/I ok- corrections made
Rough-in1/23/20201/24/20201/24/2020AFAIL
DetailsJack Reynolds
lockbox code is 7777. bj ###-#### Inspection requested via web by william kerwin
- 2nd floor bathroom exhaust needs uncovered and terminated outside in approved manner
- toe kick in kitchen needs ducted out
- fireplace installation instructions
-CSST needs full striker plates where within 2' of stud edge and half striker plates everywhere else
- secondary drain on coil needs wetswitch installed by final and pump safety wired
Pressure Test1/23/20201/24/20201/24/2020APASS
DetailsJack Reynolds
lockbox code is 7777. Inspection requested via web by william kerwin
- 20lb gas pressure test ok
- tagged meter location