Permit Information
Permit NumberMEC20-00712
StatusFinaled
Name GOMEZ MECHANICAL
Site Address 3909 W TARGEE ST
Project Name 
Customer Number011
ePlanReviewNo
Description
Alteration or Repair: increase flu pipe size , range vented and gas pressure test // adding 2x bathroom fan, 1x dryer vent van 2-27-20 GDB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/9/20204/9/20204/9/2020PPASS
DetailsJack Reynolds
Marko ***cleared*** Phone #: ###-####
- final ok
Rough-in2/27/20202/27/20202/27/2020PPASS
DetailsJack Reynolds
Marco Phone #: ###-####
- R/I ok
Rough-in2/26/20202/27/20202/27/2020AFAIL
DetailsJack Reynolds
Call half hour before // Marco Phone #: ###-####
- range vent ok b vent ok
- need to see 3 exhaust fans added to permit/ a dryer vent added to permit
- dryer vent needs proper fittings installed in wall
- by final will need to see combustion air opening for mech closet min 100sq" each opening
Rough-in2/19/20202/20/20202/20/2020AFAIL
DetailsJack Reynolds
call marco 30 minutes before arriving for home access 208 353 5484 thanks
Phone #: ###-#### Inspection requested via web by marco gomez
- common b vent needs 1" clearances
- all bathrooms need exhaust
- laundry room needs dryer vent and these items need to be added to permit
- will need to see combustion air opening high low for furnace and new location of water heater in basment
- 20lb gas pressure test ok