Pressure Test | 6/25/2020 | 6/26/2020 | 6/26/2020 | A | PASS |
Ben Livingston
|
|
|
After 10 please also please call Jordan when heading that way at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Scott Wickstrom - 20lb
|
DOC - Permit Finaled | 6/26/2020 | 6/26/2020 | 6/26/2020 | P | PASS |
Ben Livingston
|
|
|
|
Pressure Test | 6/22/2020 | 6/25/2020 | 6/25/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Scott Wickstrom 1- lower pressure gas test needs max 30 lb gauge and test above 20 psi- test was at 10psi on a 60lb gauge- 2- need to install open tee between 2 gas valves in crawl 2417.1.4 2012 IRC when tying onto existing gas piping 3- provide co detector/s if none installed retest after corrections made
|