Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberMEC20-02950
StatusIssued
Name VELOCITY HEATING & COOLING
Site Address 2393 W AIRPORT WAY
Project Name 
Customer Number5000
ePlanReviewNo
Description
New: Run Gas line from meter to package unit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Pressure Test7/18/20207/20/20207/20/2020PPASS
DetailsJack Reynolds
reinspect corrections. Phone #: ###-#### Inspection requested via web by David Dixon
- 20lb gas test ok
- tagged meter location
Pressure Test7/17/20207/17/20207/17/2020PFAIL
DetailsBrian Scoles
pressure whiteness gas line to package unit on roof. Phone #: ###-#### Inspection requested via web by David Dixon-
1- both penetrations thru wall at meter and on roof need 10 mil tape installed-
2- vertical csst in wall need supports removed needs to be free floating
3- need csst approved nail plates in exterior wall on horizontal gas piping
4- retest whole system once corrections are made