Permit NumberMIS02-00025
StatusFinaled
Name BOB COOK
Site Address 2309 N MOUNTAIN VIEW DR
Project Name 
Customer Number 
ePlanReview 
Description
**(Inspection Request)** This permit has been requested by Bob Cook for a propriety inspection of this existing office. Inspector to review office builidng onsite to determine if there are any code related requirements that need to be addressed. Reserch of building department permits indicate that remodels were performed on an B-2 occupancy / Building type VN / Land Use Zone R-1c/ Date 4/25/79. No Square footage was mentioned, no avalible floor plans to reference. NO WORK IS AUTHORIZED UNDER THIS PERMIT (rmh)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection12/8/200312/8/200312/8/2003 DONE
DetailsTom Arcoraci
BLD-Final9/20/20029/20/20029/20/2002APASS
DetailsBob Archibald
Electrical issues ok Per Jim Schmer. OK to issue CO.
Permanent Occupancy 9/20/20029/20/2002 DONE
Details
BLD-Final9/17/20029/17/20029/17/2002PPART
DetailsBob Archibald
Structural Corrections made ok. Code enforcement, Fire and plumbing issues made ok. Waiting on confermation of electrical.
FIR-Final8/6/20028/7/20028/7/2002AFAIL
DetailsTroy Cobbley
the fire alarm system for this building is not required and the existing system is not correct for current code. I left the owners with the option to upgrade the fire alarm system or to remove the existing system 8/7/2002 11:56:51 AM
COD-Conference2/14/20022/14/20022/14/2002PPART
DetailsBob Archibald
Observations based on requirements of resolution 13533.
A. Exterior exit doors require removal of thumb turn locking hardware and need to open in the direction of travel
B. Exit signage requires maintenance and relocation for visibility from any location.
C. Stairways with 2 or more risers require hand rails.
D. Conference room and offices located in basement do not meet required egress or natural light requirements.
E. Corridor system has a dead end configuration exceeding 20 feet.
F. Fire alarm system requires testing.
G. Electrical system requires review, multiple circuts observed.
H. Leaky plumbing observed in basement utility room.