BLD-Final | 3/11/2004 | 3/11/2004 | 3/11/2004 | P | PASS |
Jim Sly
|
|
|
ANDRIA PLEASE CALL FIRST ; Phone #: ###-#### Internet Inspection Request from: Darla Downs 3/11/2004 1:54:29 PM Stairs, guards etc. met code req. of which they were built....No change of Occupancy. OK for Perm Occ. :) 3/11/2004 2:14:06 PM
|
FIR-Final | 3/9/2004 | 3/11/2004 | 3/11/2004 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 3/11/2004 11:02:39 AM
|
Permanent Occupancy | | 3/11/2004 | 3/11/2004 | | DONE |
|
|
|
|
FIR-Final | 2/24/2004 | 2/24/2004 | 2/24/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide a code compliant fire alarm system per review note #2. This will require a new permit to be issued since the original was expired. Provide suite number. Repair the exit sign at the main exit. Sprinkler pendant in the women's restroom is closer than 1' from a supply register. Mount fire extinguishers at 48" above finish floor. Cover electrical junction boxes in upstairs room. Remove dead bolts on exit doors in warehouse 2/24/2004 2:26:03 PM
|