MIS-Aging Inspection | 9/6/2004 | 9/6/2004 | 9/6/2004 | | CANC |
Tom Arcoraci
|
|
|
|
BLD-Final | 7/6/2004 | 7/7/2004 | 7/7/2004 | P | PART |
Tom Arcoraci
|
|
|
bill aldrich; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok for temp 7/7/2004 11:07:48 AM
|
BLD-Final | 7/6/2004 | 7/7/2004 | 7/7/2004 | P | PART |
Tom Arcoraci
|
|
|
bill aldrich; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok for temp 7/7/2004 11:07:48 AM
|
BLD-Final | 7/6/2004 | 7/7/2004 | 7/7/2004 | P | PART |
Tom Arcoraci
|
|
|
bill aldrich; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok for temp 7/7/2004 11:07:48 AM
|
FIR-Final | 7/6/2004 | 7/7/2004 | 7/7/2004 | A | PART |
Troy Cobbley
|
|
|
Remove thumbturns from the main exit. Provide "Door to remain unlocked during buisness hours" sticker at the main exit. Provide emergency lights/exit signs per approved plans. Provide with battery backup. Second exit doors are required to swing in direction of travel (out). Provide approved hardware on the second exit doors. If double doors are used both leafs shall open in a single motion. Provide fire extinguishers as discussed. 7/7/2004 9:48:36 AM
|