Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberMIS10-00013
StatusFinaled
Name CANADA LIFE ASSURANCE CO
Site Address 415 E PARKCENTER BLVD 112
Project Name 
Customer Number 
ePlanReview 
Description
(KNOCK 'EM DEAD PRODUCTIONS DINNER/THEATRE) As directed by management, this application is for inspection to determine minimum fire & life safety requirements by inspection, in accordance with the attached list, to allow the operation of this tenant with-in suites 110 (dinner seating), 112 (theatre production) & 130 (food catering location) while tenant is preparing required submittals for Planning approval, PDS Building Division Major Tenant Improvement submittal documents for occupancy use change code compliance; CDH approval and PW approval. Life safety concerns noted during inspection will require correction before tenant can open to the public. A required exit door between Suite's 110 & 112 with panic hardware will be installed now. All required submittals for Planning & Building Divisions shall be submitted, approved, permits & CUP issued, tenant improvements completed and a Certificate of Occupancy issued for this tenant within 90 days of the issuance of this permit. CZC10-00005 drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection7/16/20107/16/20107/16/2010 PASS
DetailsJim Storey
DOC - Permit Finaled7/16/20107/16/20107/16/2010PPASS
DetailsJim Storey
MIS-Aging Inspection5/11/20105/11/20105/11/2010 PASS
DetailsJim Storey
no drinking fountian at this time june 30 th is due date.
FIR-Final3/10/20103/10/20103/12/2010PPASS
DetailsForrest France
Field verified all items on the previous issued correction notice have been finished, fire life safety passed.
FIR-Final1/22/20101/25/20101/25/2010APART
DetailsForrest France
Correction items include the following: Provide suite address numbers for spaces 110 and 130, max. height for fire extinguishers is 48" AFF, install missing escutcheons at fire sprinklers heads at various locations throughout, replace missing ceiling tile at the closet behind the sound booth, fire sprinklers at three storage rooms are overspaced- note; this work will require an FIR permit and to be performed by a licensed fire protection contractor, spacing for floor mounted obstructions at the stage area to meet NFPA 13 ch. 8 guidelines, provide a current certification for the existing type one hood suppression system in suite 130, provide approved hardware at the main entry/exit door from suite 130.
FIR-Final1/21/20101/22/20101/22/2010APART
DetailsForrest France
See eight item correction notice on site for a list of deficiencies. Noted fire sprinkler system modifications will be necessary and shall be completed by a licensed contractor via an approved fire sprinkler permit.
ELE-Final1/21/20101/22/20101/22/2010APASS
DetailsDoug A Poedy
Scott-Please meet at 12:30 per direction of Bob Archibald Phone #: ###-####. Ok final per Bob R.
BLD-Final1/21/20101/22/20101/22/2010PDEFR
DetailsJim Storey
Scott-Please meet at 12:30 per direction of Bob Archibald Phone #: ###-#### to bob
BLD-Final1/22/20101/22/20101/22/2010PPART
DetailsJim Storey
Ok for temp occ.. Correction Notice issued to complete requirements to obtain a Certificate of Occupancy.