Permit Information
Permit NumberMIS14-00162
StatusFinaled
Name LEEANDRA O'DANIEL
Site Address 7155 W USTICK RD
Project Name 
Customer Number 
ePlanReviewNo
Description
(apt B) Substandard renters complaint concrete walls in bathroom crumbling, dry rot walls and ceiling, leaking around light fixture in ceiling, electrical problems with power going out alot, exposed wires in apartment, panel box is hot to touch, concerned with not enough power supply for 4 units in building.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection5/28/20155/28/20155/28/2015 DONE
DetailsBob Archibald
DOC - Permit Finaled5/28/20155/28/20155/28/2015PPASS
DetailsBob Archibald
MIS-Aging Inspection1/27/20151/27/20151/27/2015 DONE
DetailsBob Archibald
ELE-Conference9/22/20149/22/20149/22/2014PFAIL
DetailsRock A. Hudson
Due to no activity securing permit from electrical contractor for service uupgrade to solve over heating issues. Section 4-05-28 ENFORCEMENT THROUGH DISCONNECTION OF POWER
It shall be unlawful for any person, firm, association or corporation to install electrical wiring, equipment,
apparatus or fixtures in violation of any rule or provision of this code or to use, cause or permit to be used
any electrical installation that is hazardous to life or property within Boise City.
A. If the Electrical Inspector shall find any part of any electrical wiring, equipment,
apparatus or fixture in, on or about any building or premise in Boise City to have been
installed or altered without an electrical permit or not in compliance with the rules of this
Boise Municipal Code
Page 12 of 17
SUPPLEMENT NO. 42
Code or if any electrical wiring, equipment, apparatus or fixture is found to be immediate
hazardous to life and property, the Electrical Inspector shall have the right and authority
to cause such installation to be disconnected and to place a written correction notice upon
the disconnected installation. The Inspector shall, at the same time, give notice of such
disconnection to the owner or occupant of the building or premise and/or to the person(s)
using electric current carried by the disconnected installation that the disconnection has
been made.
Such notice shall be made by the most reasonably effective means and a written notice. Posted correction notice informing of action.
BLD-Conference7/18/20147/23/20147/28/2014ADONE
DetailsJim Sly
LeeAndra ###-#### No life safety issues except Electrical. Deferred to Electrical and Mechanical. Mechanical contacted because new furnace and AC installed without permit, and need to verify that system is supplying only one space (unit).
DOC - Permit Finaled7/28/20147/28/20147/28/2014PPASS
DetailsJim Sly
ELE-Conference7/18/20147/25/20147/25/2014ADONE
DetailsRock A. Hudson
Reinspect unit for corrections compiance. Spoke with owner of bldg and explained the over heating issue. They are getting bids to correct electric issues. Tenant in unit A has moved out. Due to reduced demand at this time main breaker feeding 7155 is cool to touch as well as sub panel feeders. Will re check in 2 weeks.
ELE-Conference7/25/20148/8/20147/25/2014ACANC
DetailsRock A. Hudson
Reinspect unit for corrections compiance
BLD-Conference7/16/20147/18/20147/18/2014ACANC
DetailsJim Sly
(apt B) Substandard renters complaint concrete walls in bathroom crumbling, dry rot walls and ceiling, leaking around light fixture in ceiling, electrical problems with power going out alot, exposed wires in apartment, panel box is hot to touch, concerned with not enough power supply for 4 units in building.// Leeandra ###-####

No Imminent structural hazards. Electrical to investigate Electr problems. Rock Hudson.
MEC-Conference7/18/20147/18/20147/18/2014PPART
DetailsAlan Hauser
(apt B) per electrical inspector A/C unit installed without permit causing overload on electrical system.owner number is ###-#### ron and sharon kirkoman. talked to owner he was unaware that contractor had not pulled permit, will take care of it he said.
ELE-Conference7/16/20147/18/20147/18/2014AFAIL
DetailsRock A. Hudson
(apt B) Substandard renters complaint concrete walls in bathroom crumbling, dry rot walls and ceiling, leaking around light fixture in ceiling, electrical problems with power going out alot, exposed wires in apartment, panel box is hot to touch, concerned with not enough power supply for 4 units in building.// Leeandra ###-#### BCC 4-05-18- lectrical permit required on AC unit added to Appt. A.
NEC 230.72(C)- Each tenant shall have access to accupants service.
NEC 230.79(C)- Each appt. single family dwelling and shall have minimum service rating of 100 amps for each unit.
Bldg originally designed for duplex. Building owner shall seek conditional use approval for use as 4-plex.
7 days to secure electrical contractor for over load issue.
7 days to secure mechanical permit for HVAC equiptment added.