DOC - Permit Finaled | | | 5/10/2018 | | PASS |
|
|
|
permits issued
|
PLM-Final | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PASS |
Bill VanDegrift
|
|
|
Nicholas Phone #: ###-#### permits pulled
|
DOC - Permit Finaled | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PASS |
Bill VanDegrift
|
|
|
Nicholas Phone #: ###-#### permit pulled
|
MEC-Final | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PASS |
Bill VanDegrift
|
|
|
Nicholas Phone #: ###-#### mec permit pulled
|
PLM-Final | 3/13/2018 | 3/15/2018 | 3/15/2018 | A | FAIL |
Dan Ediger
|
|
|
NIcholas Phone #: ###-#### for restaurant occupancy The double check and rp are run in series. 1. The carbonator must have a dedicated rp backflow assembly. 2. The ice tea machine must be served by a rp backflow assembly. 3. Install airgaps on both rp's and pipe to the floor sink. 4. Support the backflow assemblies on the outlet side. 5. The plumber must pull a permit and schedule an inspection. 6. If the ice maker has a pre-filter installed then it must be protected by a double check.
|
MEC-Final | 3/13/2018 | 3/15/2018 | 3/15/2018 | A | FAIL |
Brian Scoles
|
|
|
NIcholas Phone #: ###-#### for restaurant occupancy- need to tether all appliances discussed- needs splash shield installed between fryer and open flame top- need mech or plumbing permit pulled for gas work- need air balance report- Nichalos knows about these issues
|