MEC-Final | 8/11/2020 | 8/12/2020 | 8/12/2020 | A | PASS |
Jack Reynolds
|
|
|
please call Joe on your way Phone #: ###-#### Inspection requested via web by Misty McNabb
|
FIR-Final | 8/10/2020 | 8/10/2020 | 8/11/2020 | P | PASS |
Troy Cobbley
|
|
|
Duct smoke detector tested/witnessed and it did function for shutdown.
|
FIR-Final | 7/22/2020 | 7/22/2020 | 7/22/2020 | P | FAIL |
Troy Cobbley
|
|
|
Inspecton turned into conference. Need to test with the heat on and with smoke. Need remote annunciator.
I have an RTU change out at 4750 Overland mechanical permit MEC20-02775 with a smoke detector installed stand alone. The contractor is Total System Services techs name is Joe and his number is ###-####. If you have any more question let me know.
|