Permit Information
Permit NumberNAF14-00022
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 12653 ANDY'S GULCH DR
Project NameHILLIARD RESIDENCE
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a two level single family dwelling. The dwelling is protected using NFPA 13D. The piping is CPVC with extended coverage residential sprinklers.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final8/6/20158/6/20158/6/2015PPASS
DetailsKatie Marron
Previous tank and pump correction items satisfactorily completed. Flow test complete. Scope of work completed satisfactorily. Permit Finaled.
INSP-Final7/31/20158/3/20158/3/2015PNR
DetailsKatie Marron
Per call with Anthony still waiting on plumbing contracto to install water spigot to sprinkler tank.
INSP-Final7/31/20157/31/20157/31/2015PCANC
DetailsTroy Cobbley
Call Anthony when you are headed that way. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Final7/28/20157/29/20157/29/2015PCANC
DetailsThomas Walsh
Not ready for inspection. Tank fill line not completed and pump not pre-tested yet. Will reschedule when these items are conpleted.
INSP-Sprinkler Rough-in6/1/20156/4/20156/4/2015PPASS
DetailsKatie Marron
Tenting completed satisfactory. One spot in middle bedroom, 1st flr identified as needing minor adjustments to tighten down insulation on side of pipe..
INSP-Sprinkler Rough-in6/1/20156/1/20156/1/2015PCANC
DetailsKatie Marron
Tenting inspection -please try to come later in the day if possible. Call Anthony with questions. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/21/20154/21/20154/21/2015APART
DetailsKatie Marron
Scope of work good to tent with the following exceptions. Heads are missing in mud room and over water heater closet on first floor, per plan. Provide heads or justification for exception according to NFPA 13D. **Per phone discussion with Anthony, hallway head provides exceptable coverage to mudroom in accordance with NFPA 13D 8.2. Additionally water heater is no longer located in that closet so head no longer required since space is less than 24 sqft per chapter 6.

Items remaining, tank requires hose bib to main water supply and flow switch to be tested once hooked into alarm system NACFR 2008-013