Permit Information
Permit NumberNAF15-00043
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10482 W CARLTON BAY DR
Project NamePRIMARY HEALTH
Customer Number 
ePlanReviewNo
Description
[Primary Health Corporation]
The fire sprinkler scope of work consists of new tree addition from the riser. The new addition is office area.

(PRIMARY HEALTH) Permit for the construction of a new 5,600 sq. ft. addition to an existing 7,730 sq. ft. Primary health office building with work to include general site work, electrical, plumbing and mechanical. The new addition will include general office areas, a training room and two new restrooms per the approved plans, attached engineering and any notations. This building is fully fire sprinklered for area increase. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final5/19/20165/20/20165/20/2016PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro5/19/20165/20/20165/20/2016PPASS
DetailsTroy Cobbley
Overhead hydro passed
INSP-Sprinkler Rough-in/Hydro5/19/20165/19/20165/19/2016PFAIL
DetailsTroy Cobbley
Overhead hydro failed again due to loss of pressure
INSP-Sprinkler Rough-in/Hydro5/18/20165/19/20165/19/2016AFAIL
DetailsTroy Cobbley
Overhead hydro failed due to visible loss of pressure at the guage.
INSP-Sprinkler Rough-in/Hydro5/17/20165/18/20165/18/2016PFAIL
DetailsTroy Cobbley
Test failed due to a split valve. Rescheduled for tomorrow
INSP-Conference5/5/20165/6/20165/6/2016ADONE
DetailsKatie Marron
Discussed requirements for occupancy with Mike (superintendent).
INSP-Sprinkler Rough-in4/14/20164/14/20164/14/2016PPEND
DetailsKatie Marron
Rough-in inspection completed. Verified all uprights and pendant drops. One hangar missing see plans on site. Hangar will be visible at final from drop ceiling.
OK to cover PENDING resubmitted calcs for remote area 2 due to two sprinkler heads added to the calc area.
INSP-Sprinkler Rough-in3/31/20164/1/20164/1/2016ACANC
DetailsJim Page
Inspection request cancelled, point of contact on job could not get a set of approved resubmittal blue prints to have for inspection. Contractor will reschedule inspection for later date.
INSP-Sprinkler Rough-in3/21/20163/22/20163/22/2016PFAIL
DetailsTroy Cobbley
Plan modifications needed due to extensive changes needed such as adding upright sprinkler coverage that is missing is some locations and additional fittings have been added in the mains and riser nipples.