Permit Information
Permit NumberNAF16-00007
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 416 E 49TH ST Unit: BLDG C
Project NameLEGACY APARTMENT BLDG C
Customer Number 
ePlanReviewNo
Description
[Legacy Apartments Building C]
The fire sprinkler scope of work consists of 3 level apartment building protected by a NFPA 13R wet system. There is a small amount of heat tracing where the main crosses the open corridor.

See NAF15-00040 for the underground permit
See NAF15-00030 for building fire code plan review.

Legacy Apartment building "C". Permit for a new 3 story 24,116 sqft apartment building consisting of 24 units. Each dwelling unit shall contain an emergency guide in accordance with IFC section 408.9 indicating evacuation routes, smoke alarms and building fire extinguisher locations. This building is required to be fire sprinklered with an approved fire alarm system in accordance with NFPA 13 and NFPA 72. Separate fire protection permits will be required; as regulated by North Ada County Fire & Rescue District. SJA
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final12/13/201612/14/201612/14/2016PPASS
DetailsKatie Marron
Systems test completed satisfactory. Scope of work complete. Permit finaled.
INSP-Sprinkler Rough-in/Hydro9/7/20169/8/20169/8/2016APASS
DetailsKatie Marron
Hydrostatic test for all flrs and remote fdc completed satisfactory. FDC roughin complete. Heat trace on third floor installed.

Tenting inspection on third floor: at the time of inspection tenting was satisfactory.
INSP-Sprinkler Rough-in9/1/20169/1/20169/1/2016ADONE
DetailsKatie Marron
Completed 8/31/16. Rough-in for third floor complete. All side wall sprinklers on all floors complete, mains from riser up are completed.

Still to be completed:
-tenting third floor
-heat trace on all floors/breezeways
-remote FDC
INSP-Sprinkler Rough-in8/16/20168/17/20168/17/2016PDONE
DetailsKatie Marron
Rough-in 1st & 2nd floor completed satisfactory. Two missing hangars fixed on the spot. **Sidewalls and riser not installed, these areas must remain uncovered for inspection.**
INSP-Sprinkler Rough-in/Hydro8/11/20168/16/20168/16/2016ACANC
DetailsKatie Marron
Inspection called in under building system permit. Was completed and recorded on correct UDG permit.