Permit Information
Permit NumberNAF16-00010
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 445 E 50TH ST Unit: BLDG D
Project NameLEGACY APARTMENT BLDG D
Customer Number 
ePlanReviewNo
Description
[Legacy Apartments Building D]
The fire sprinkler scope of work consists of 3 level apartment building protected by a NFPA 13R wet system. There is a small amount of heat tracing where the main crosses the open corridor.

See NAF15-00041 for the underground permit
See NAF15-00032 for building fire code plan review.

Legacy Apartment building "D". Permit for a new 3 story 24,116 sqft apartment building consisting of 24 units. Each dwelling unit shall contain an emergency guide in accordance with IFC section 408.9 indicating evacuation routes, smoke alarms and building fire extinguisher locations. This building is required to be fire sprinklered with an approved fire alarm system in accordance with NFPA 13 and NFPA 72. Separate fire protection permits will be required; as regulated by North Ada County Fire & Rescue District. SJA
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final5/15/20175/17/20175/17/2017PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro5/4/20175/5/20175/5/2017PPASS
DetailsScott Arellano
Hydro test for systems 1, 2, & 3 building "D" Pass
INSP-Sprinkler Rough-in2/21/20172/22/20172/22/2017APASS
DetailsKatie Marron
Rough in and tenting inspection for remaining sections of building. Verified heat tape at all six breezeways. Verifed vertical FDC pipe with ball drip. At time of inspection tenting OK.

All units ok to cover besides two spaces with missing drops; one at the second flr and one at the third flr (see plans)
INSP-Sprinkler Rough-in2/6/20172/7/20172/7/2017PPASS
DetailsTroy Cobbley
The FDC piping in the first floor apartment is complete except for the piece down the wall with the ball drip. Piping in the apartment is ok for cover. Vertical piece can be verified at the next inspection.
INSP-Sprinkler Rough-in2/2/20172/6/20172/6/2017APART
DetailsTroy Cobbley
See the city approved plans for the seven apartments, 1st/2nd floors, where rough-in is passed and piping can be covered. One apartment as noted on the 1st floor can not be covered since the piping to the FDC has not been installed. Piping in the breeze way can not be covered until the heat tape is verified.