Permit NumberNAF16-00017
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY
Site Address 201 E 41ST ST
Project NameJIMMY'S AUTO BODY
Customer Number 
ePlanReviewNo
Description
Pre-engineered dry chemical system for spray paint booth.

Note: The dry chemical system does not remove the requirement for fire sprinklers in the spray paint booth, if the building is to be considered a fully sprinklered building. Fire sprinklers are still required. (Ref: NFPA 13: 4.1 and 22.4)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final3/24/20163/28/20163/28/2016PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro3/7/20163/8/20163/8/2016ADONE
DetailsTroy Cobbley
Todays inspection request was a conference to discuss the classI electrical at the door to the paint booth. The contractor is to meet the 3' vertical and 5' horizontal requirement for the class I wiring. Also per Scott and my discussion the owner is to provide signage at both sides of the overhead doors (no smoking, no welding, no grinding..ect.) instead of meeting the 6' clearance requirement from exterior walls. The 6' requirement can't be met due to meeting the 30' from property line requirement. All references are derived from the 2012 IFC chapter 24.
INSP-Final3/2/20163/3/20163/3/2016AFAIL
DetailsKatie Marron
Inspection failed. The following items need to be corrected and reinspected:
-Plan modification required for installed piping changes.
-System Test
-Exhaust ventilation per IFC 2404.7.6 specifically meeting 6' from exterior wall
-Electrical wiring per IFC 2404.9.4 (explosion proof outlets and exit sign)

4A-40BC fire extinguisher installed during inspection.