Permit Information
Permit NumberNAF16-00032
StatusFinaled
Name PROTEX
Site Address 5024 W CHINDEN BLVD
Project NameWEST VET
Customer Number 
ePlanReviewNo
Description
Provide a new fire alarm system with voice evacuation in a new building. Associated with Garden City Case Number BLD2015-00091 / GCB15-00090.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final11/21/201611/22/201611/22/2016APASS
DetailsKatie Marron
Verified previous items. Scope of work complete. Permit Finaled.
INSP-Final11/21/201611/21/201611/21/2016PFAIL
DetailsKatie Marron
Verified all devices. Xray room missing a device, device on balcony was not functioning, and pressure switch on dry system not connected to bell. Smokes at main panel and riser room to be tested as well.

-RTU detectors were tested, OK
-Elevator recall tested, OK
-All Tampers, Flows tested
INSP-Final11/16/201611/21/201611/21/2016APASS
DetailsKatie Marron
All previous correction items were completed. Air Test had been completed previously on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
INSP-Final11/16/201611/18/201611/16/2016ACANC
DetailsTroy Cobbley
Phone #: 5015792 >> Inspection requested via mobile web by Dirk Inspection cancelled via mobile web on Wednesday, November 16, 2016.