INSP-Final | 11/21/2016 | 11/22/2016 | 11/22/2016 | A | PASS |
Katie Marron
|
|
|
Verified previous items. Scope of work complete. Permit Finaled.
|
INSP-Final | 11/21/2016 | 11/21/2016 | 11/21/2016 | P | FAIL |
Katie Marron
|
|
|
Verified all devices. Xray room missing a device, device on balcony was not functioning, and pressure switch on dry system not connected to bell. Smokes at main panel and riser room to be tested as well.
-RTU detectors were tested, OK -Elevator recall tested, OK -All Tampers, Flows tested
|
INSP-Final | 11/16/2016 | 11/21/2016 | 11/21/2016 | A | PASS |
Katie Marron
|
|
|
All previous correction items were completed. Air Test had been completed previously on 9/20/16. System test completed satisfactory. Scope of work complete. Permit Finaled.
|
INSP-Final | 11/16/2016 | 11/18/2016 | 11/16/2016 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 5015792 >> Inspection requested via mobile web by Dirk Inspection cancelled via mobile web on Wednesday, November 16, 2016.
|