INSP-Final | 11/21/2016 | 11/22/2016 | 11/22/2016 | A | PASS |
Katie Marron
|
|
|
24 Hr Air Test completed satisfactory. Phone #: ###-####
|
INSP-Sprinkler Rough-in | 11/17/2016 | 11/21/2016 | 11/21/2016 | A | PART |
Katie Marron
|
|
|
24 air test began at 9:40 am on 11/21/16. Pressure was 42psi
|
INSP-Sprinkler Rough-in/Hydro | 11/17/2016 | 11/17/2016 | 11/17/2016 | A | PASS |
Katie Marron
|
|
|
Hydrostatic test of FDC, Dry system and Wet system completed satisfactory.
24 hr air test still needed for dry system.
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2016 | 11/16/2016 | 11/16/2016 | P | FAIL |
Katie Marron
|
|
|
Hydro was not able to be completed as Riser room was locked upon return after 2 hour period.
|
INSP-Sprinkler Rough-in/Hydro | 11/14/2016 | 11/15/2016 | 11/15/2016 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro tests failed due to visible leak on the ground and pressure loss at the guages. I also noted that the supply piping to the FDC needs hydro tested.
|
INSP-Sprinkler Rough-in/Hydro | 11/14/2016 | 11/14/2016 | 11/14/2016 | P | CANC |
Troy Cobbley
|
|
|
Not ready for hydro test due to leak.
Please Contact Perly Daniels 30 minutes before inspection Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 11/9/2016 | 11/10/2016 | 11/10/2016 | P | PART |
Katie Marron
|
|
|
Rough in for dry and wet system completed. Grid areas ok to cover. Correction item: Per note on plans earthquake bracing into wood shall be through bolted, contractor to correct and provide verification (photos).
|
INSP-Sprinkler Rough-in/Hydro | 10/26/2016 | 10/27/2016 | 10/27/2016 | A | FAIL |
Troy Cobbley
|
|
|
Stopped rough-in inspection on the dry system due to pipe routing changes including in the remote area. Stopped the rough-in inspection on the wet system due to pipe routing changes in the main that effects the remote area. I also noted a branchline size the did not match plan. Plans need to be re-submitted showing all pipe routing changes. Fitter is using 1/2 lag bolts in the bottom of the 2x6 structure. I need to verify that is ok.
|