DOC - Permit Finaled | | | 7/6/2017 | | DONE |
|
|
|
as per Lee M and Scott A.-permit is complete
|
INSP-Final | 6/29/2017 | 6/30/2017 | 6/30/2017 | A | FAIL |
Troy Cobbley
|
|
|
Plan modifications are required for the changes in the candellas of the wall mounted strobes in the Residence Rooms. I verified the fire sprinkler interconnections with the existing fire alarm panel but stopped the inspection after finding multiple wall mount strobes overspaced in the Resident Rooms. I have not tested horns, strobes, smoke detectors, door release or hvac shutdown.
|
INSP-Final | 6/30/2017 | 6/30/2017 | 6/30/2017 | P | PASS |
Scott Arellano
|
|
|
Re-inspection after plan modification. Pass.
|