Permit Information
Permit NumberNAF17-00023
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 4379 W CHINDEN BLVD
Project NameADVANCE AUTO PARTS
Customer Number 
ePlanReviewNo
Description
[Advanced Auto Parts]
The fire sprinkler scope of work consists of single level fire wet system with a 4” underground 3” backflow, 4” riser, lO sprinklers, utilizing a 3”x3”x2”. The storage height is undetermined at this time.

• The fire protection underground piping is under permit NAF17-00020

[NAF17-00007] - Permit to construct a new 14,990 sq. ft. auto parts store. Store has two retail areas, a commercial pick up area and retail area. The racks shown are not included under this permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final8/24/20178/25/20178/25/2017ADONE
DetailsTroy Cobbley
permit finaled
DOC - Permit Finaled  8/25/2017 DONE
Passed final per Troy
INSP-Final8/9/20178/11/20178/11/2017AFAIL
DetailsTroy Cobbley
Repair the retaining straps, provide the calc sticker and provide the updated approved drawings for the earthquake bracing locations
INSP-Sprinkler Rough-in/Hydro8/3/20178/4/20178/4/2017APART
DetailsTroy Cobbley
Inspection turned into a conference. Hydro test has already been performed. Earth quake bracing is not installed in the approved locations. It will need to be installed as approved or calculations resubmitted for the new locations. Retaining straps are still not installed correctly. Need cap on FDC. Need sticker on bell. Need service tag on riser. Need data sheet on the test valve that it has the correct orfice for the inspector test. Need forward flush done. And ultimately need the fire alarm interconnections verified.
INSP-Sprinkler Rough-in/Hydro7/17/20177/17/20177/17/2017APART
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping complete. Sway bracing installation does not match what is on the city approved drawings, sway bracing will need to be repaired, numerous retaining straps throughout space are not installed correctly (straps found need to be bent around truss to retain beam clamp) As-builts will need to be completed and submitted for pipe that was installed around HVAC penetrations through deck.